Pregunta 1

Pregunta
Run-outs from horizontal mains or branches shall be taken off ___ the centerline of the pipeline
Respuesta
  • Above
  • Below
  • At
  • Any of the above

Pregunta 2

Pregunta
While brazing medical gas copper joints, a purge gas shall flow continuously to prevent the formation of copper oxide on the inside surface of the joint. What shall be used as a purge gas?
Respuesta
  • Oil Free Dry Argon MD
  • Oil Free Dry Helium NF
  • Oil Free Dry Nitrogen NF
  • Any Inert Gas

Pregunta 3

Pregunta
Which of the following filler metals shall be used to braze copper to copper joints in medical gas/vacuum distribution piping?
Respuesta
  • BAg Series
  • BAu Series
  • BCup Series
  • BNi Series

Pregunta 4

Pregunta
Tubing for positive pressure medical gas systems delivered from the manufacturer shall be _____
Respuesta
  • Plugged or capped
  • Harddrawn seamless
  • Identified as "oxy" or "med"
  • All of the above

Pregunta 5

Pregunta
In positive pressure systems area alarm sensors for vital life support and critical care areas shall be located on which side of the zone valve box assemblies.
Respuesta
  • Patient side
  • Outlet/Inlets side
  • Downstream side
  • All of the above

Pregunta 6

Pregunta
The master alarm systems shall activate when the pressure in the main supply lines increase or decrease by _____ percent.
Respuesta
  • 10
  • 20%
  • 40
  • 50

Pregunta 7

Pregunta
All medical gas alarm system shall have a _______ audible indication for each conditioned monitor
Respuesta
  • Adjustable
  • Cancelable
  • Optionable
  • All of the above

Pregunta 8

Pregunta
The master alarm systems shall consists of two or more alarm panels, a centralized computer system shall not be permitted to be used as a substitute for one of the required master alarm panels.
Respuesta
  • True
  • False

Pregunta 9

Pregunta
Since dew point and carbon monoxide monitors are located upstream of the source valve, demand check fittings are not required.
Respuesta
  • True
  • False

Pregunta 10

Pregunta
Where shall pressure indicators be provided for medical gas systems.
Respuesta
  • On the main supply
  • At the area alarm
  • Outlet/Inlets side of the zone valve
  • All of the above

Pregunta 11

Pregunta
The scale range of positive pressure analog indicators shall have the normal reading fall within the ___ percentage of the gauge scale
Respuesta
  • 25
  • 50
  • 75
  • 100

Pregunta 12

Pregunta
Station inlets for WAGD service shall be legibly marked to identify them and shall be of a type appropriate for the flow and vacuum level required by the facility gas anesthetic machine.
Respuesta
  • True
  • False

Pregunta 13

Pregunta
The factory installed tubing on station outlets/inlets shall extend no further than ____ from the body of the terminal
Respuesta
  • 6
  • 8
  • 10
  • 12

Pregunta 14

Pregunta
Each station outlet/inlet for medical gas or vacuum shall be ____
Respuesta
  • Interchangeable
  • Gas-specific
  • Threaded
  • Quick-coupler

Pregunta 15

Pregunta
What is name given to the shutoff valve installed on all lateral branch piping form a main or riser?
Respuesta
  • Riser
  • Service
  • Zone

Pregunta 16

Pregunta
A shutoff valve shall be placed at the immediate connection of each source system to the distribution piping system. What is the name given to the valve?
Respuesta
  • Main
  • Supply
  • Source
  • Isolation

Pregunta 17

Pregunta
All valves except zone valve box assemblies shall be
Respuesta
  • In a secured areas
  • locked or latched
  • Labeled appropriately
  • All of the above

Pregunta 18

Pregunta
Where instrument air system are provided with standby headers
Respuesta
  • True
  • False

Pregunta 19

Pregunta
What is the minimum number of compressor required in an instrument air system that employs a standby headers?
Respuesta
  • 0
  • 1
  • 2
  • 3

Pregunta 20

Pregunta
Instrument air system shall be permitted to interconnect with medical air systems that have at least two or more compressors.
Respuesta
  • True
  • False

Pregunta 21

Pregunta
The quality of the instruments air shall be ___.
Respuesta
  • Filtered to .01 micron
  • Free of liquids
  • Free of hydrocarbons vapors
  • All of the above

Pregunta 22

Pregunta
A level 1 dedicated WAGD source shall consist of ____or more producers, each shall be sufficient to serve the peak calculated demand.
Respuesta
  • one
  • Two
  • Three
  • All of the above

Pregunta 23

Pregunta
Vacuum receivers shall be capable of withstanding a gauge vacuum of ____ inches of mercury.
Respuesta
  • 29
  • 29.9
  • 30
  • All of the above

Pregunta 24

Pregunta
Level 1 medical-surgical vacuum sources shall consist of an automatic means to prevent ____ through any of-cycle vacuum pump.
Respuesta
  • Pressure loss
  • Back pressure
  • Backflow
  • All of the above

Pregunta 25

Pregunta
Carbon monoxide shall activate the required alarms when the CO level exceeds ____.
Respuesta
  • 5 ppm
  • 10 ppm
  • 15 ppm
  • 20 ppm

Pregunta 26

Pregunta
Where charcoal filters are required, a color-metric hydrocarbon indicator shall be provided.
Respuesta
  • True
  • False

Pregunta 27

Pregunta
Where liquid ring compressors are used, air receivers shall be equipped with a high water level sensor that activates a ____alarm indicator.
Respuesta
  • Master
  • Area
  • Local
  • All of the above

Pregunta 28

Pregunta
The compressor air intakes shall be located outdoors above roof level at a minimum distance of ____ above ground.
Respuesta
  • 40 ft
  • 30 ft
  • 20 ft
  • 10 ft

Pregunta 29

Pregunta
Where medical air piping systems at different operating air pressures are required, the piping shall separate after the _____.
Respuesta
  • Filters
  • Final regulators
  • Riser valves
  • Source Valve

Pregunta 30

Pregunta
If dryers, filters and regulators are sized to serve the peak calculated demand, they shall not be duplexed.
Respuesta
  • True
  • False

Pregunta 31

Pregunta
Level 1 Medical air compressors shall be sized to served the peak calculated demand and in no case shall there be fewer than ____ compressors.
Respuesta
  • One
  • Two
  • Three
  • Four

Pregunta 32

Pregunta
Receivers for medical air shall be equipped with ____.
Respuesta
  • Relief valve
  • Automatic and manual drains
  • Sight glass
  • All of the above

Pregunta 33

Pregunta
______ connectors shall connect the air compressors with their intake and outlet piping.
Respuesta
  • Anti-vibration
  • Dielectric
  • Insulated
  • Flexible

Pregunta 34

Pregunta
Compressors for medical air shall be designed to prevent introduction of contaminants or liquid into the piping systems.
Respuesta
  • True
  • False

Pregunta 35

Pregunta
Medical air sources shall be used only for ____and calibration of medical respiratory devices.
Respuesta
  • Human respiration
  • Air-operating device
  • Instrument air
  • All of the above

Pregunta 36

Pregunta
Where the bulk cryogenic liquid oxygen supply systems is outside of and remote from the building served a ___connection shall be installed.
Respuesta
  • Maintenance cleanout
  • Refilling
  • Emergency oxygen supply
  • All of the above

Pregunta 37

Pregunta
An in building emergency reserve system can be substituted for the EOSC.
Respuesta
  • True
  • False

Pregunta 38

Pregunta
Bulk cryogenic liquid system site shall have allowance for at least ___ of clearance around storage container, vaporizer and the pressure regulating manifold.
Respuesta
  • 2 ft
  • 3 ft
  • 4 ft
  • 5 ft

Pregunta 39

Pregunta
Installers of bulk cryogenic liquid systems shall be qualified to meet CGA M-1 Standard, Guide for Medical Gas Installations at Consumer Sites.
Respuesta
  • True
  • False

Pregunta 40

Pregunta
manifolds for cryogenic liquid cylinder shall indicate when or at a predetermined set point before the reserve contents fall to one day's average supply, indicating ____.
Respuesta
  • Reserve is in use
  • Primary empty
  • Secondary empty
  • Reserve low

Pregunta 41

Pregunta
Manifolds for cryogenic liquid cylinders shall consist of ____ equal headers, each having sufficient number of liquid containers for an average day's supply.
Respuesta
  • 4
  • 3
  • 2
  • 1

Pregunta 42

Pregunta
Manifolds for gas cylinders without reserve shall consist of ____ equal headers, each with an average days supply, but not fewer than ____ connections.
Respuesta
  • Four-four
  • Three-three
  • Two-two
  • One-one

Pregunta 43

Pregunta
Relief valves shall be vented to the ____, except compressed air systems having less than 3000 cu ft at STP
Respuesta
  • Floor
  • Sewer Drain
  • Back into the systems
  • Outside

Pregunta 44

Pregunta
All pressure relief valve shall be made of brass, bronze or ___.
Respuesta
  • Stainless
  • Carbon steel
  • Cast Iron
  • Copper

Pregunta 45

Pregunta
Louvered openings for natural ventilation shall have a minimum free area of ___.
Respuesta
  • 60 sq in
  • 62 sq in
  • 70 sq in
  • 72 sq in

Pregunta 46

Pregunta
Locations for central supply systems and the storage of medical gases shall be secured with lockable doors or gates.
Respuesta
  • True
  • False

Pregunta 47

Pregunta
Cylinders in use and in storage shall be prevented from reaching temperatures in excess of ___.
Respuesta
  • 100 F
  • 130 F
  • 160 F
  • 190 F

Pregunta 48

Pregunta
Which of the following systems shall not be permitted to be located in the same indoor enclosure?
Respuesta
  • Bulk cryogenic liquid system
  • Manifolds for cryogenic liquid cylinders
  • Manifolds for gas cylinders with or without reserve
  • instrument air standby leader

Pregunta 49

Pregunta
liquid containers shall have additional product identification visible from all directions with a minimum of ____inch high letters such as 360 degree wrap around tape for medical liquid containers
Respuesta
  • 1 in
  • 2 in
  • 3 in
  • 4 in

Pregunta 50

Pregunta
Which of the following hazards shall be considered in the design, installation, testing and maintenance of medical gas and vacuum piping systems?
Respuesta
  • Contaminations
  • Fire and Smoke
  • Fire and explosions
  • Water and Gas
Mostrar resumen completo Ocultar resumen completo

Similar

Todos los Países del Mundo y sus Capitales
maya velasquez
Anatomía del Sistema Respiratorio
edonoso
CÁLCULO MENTAL
JL Cadenas
Práctica de Biología para la Prepa 1
Raúl Fox
Linea de tiempo PLANEACION ESTRATEGICA
Tactica Artico
Tipos de Fracciones
lesly.ladron
CUADRO SINOPTICO DEL DESARROLLO SUSTENTABLE
Correa Comajoi
EL MITO DE LA CAVERNA
Cardys Colorado
TÁCTICA 1.1 HISTORIA Y TRADICIONES
antonio del valle
ESTRUCTURAS REPETITIVAS O CICLICAS EN PROGRAMACION
Karla Moreno