What type of system consists of cables that were installed in an air-handling space prior to mandated use of cables that meet the flame-spread and smoke-index requirements of codes, standards & regulations?
Respuesta
  • Grandfathered System
  • Abandoned cable System
  • Riser Cable System
  • Non-Plenum Cable System

Pregunta 2

Pregunta
What are the 2 key components of an optical fiber?
Respuesta
  • Core & Cladding
  • Core & Acrylate
  • Cladding & Acrylate
  • Core & Buffer

Pregunta 3

Pregunta
The [blank_start]F Rating[blank_end] is the amount of time in hours the firestopping system can prevent flames from passing through the system.
Respuesta
  • F Rating
  • T Rating
  • L Rating

Pregunta 4

Pregunta
This is the establishment of a reference for the electrical power source (AC or DC), electrical equipment or both
Respuesta
  • Grounding
  • Bonding
  • Electrode System
  • TMGB

Pregunta 5

Pregunta
The [blank_start]L Rating[blank_end] indicates a firestops ability to provide an effective smoke seal.
Respuesta
  • L Rating
  • F Rating
  • T Rating

Pregunta 6

Pregunta
This provides a quick graphical representation of how a circuit is laid out
Respuesta
  • Circuit Layout Record
  • Cutover Plan
  • As-built

Pregunta 7

Pregunta
A Consolidation Point (CP) should serve up to 24 work areas?
Respuesta
  • True
  • False

Pregunta 8

Pregunta
How many walls of a TR should have fire-retardant plywood?
Respuesta
  • 2
  • 1
  • 3
  • 4

Pregunta 9

Pregunta
Cross-Connect Field Colors: Second-Level Backbone
Respuesta
  • Gray
  • Orange
  • White
  • Brown

Pregunta 10

Pregunta
All ferrous metal pathways must be bonded at both ends regardless of length when containing a bonding conductor?
Respuesta
  • True
  • False

Pregunta 11

Pregunta
This amount of current will cause breathing to become difficult
Respuesta
  • 2-3mA
  • 10mA
  • 50-100mA
  • 100mA

Pregunta 12

Pregunta
Who's responsibility is it to provide safety training for its employees?
Respuesta
  • Employee's Organization
  • Employee
  • OHSA
  • Customer

Pregunta 13

Pregunta
Widening or spreading out of modes in a light pulse as it progresses along the optical fiber
Respuesta
  • Dispersion
  • Core
  • Photons
  • Modal Bandwidth

Pregunta 14

Pregunta
This type of cutover is one continuous process until competed
Respuesta
  • Flash Cutover
  • Phased Cutover
  • Complete Shutdown
  • Continuous Cutover

Pregunta 15

Pregunta
This type of backbone cabling distributes telecommunications services between telecommunications spaces within a single building
Respuesta
  • Intrabuilding
  • Interbuilding
  • Fiber Optic

Pregunta 16

Pregunta
What is the width of the TMGB
Respuesta
  • 3.94 inches
  • 3.95 inches
  • 3.93 inches
  • 4 inches

Pregunta 17

Pregunta
The ITS installer can substitute products that are not part of the qualified firestop assembly
Respuesta
  • True
  • False

Pregunta 18

Pregunta
This firestop is used primarily for large air handling & exhaust vents
Respuesta
  • Blankets
  • Spray
  • Pillows
  • Foam

Pregunta 19

Pregunta
This type of cutover procedure has portions of the old system transferred to the new system in groups
Respuesta
  • Flash Cutover
  • Phased Cutover
  • Staged Cutover
  • Continuous Cutover

Pregunta 20

Pregunta
What is the information carrying capacity of a system
Respuesta
  • Bandwidth
  • Megabit
  • Megahertz
  • Decibel

Pregunta 21

Pregunta
What is the maximum length of FMT
Respuesta
  • 20 feet
  • 10 feet
  • 15 feet
  • 25 feet

Pregunta 22

Pregunta
26 AWG has ______ more attenuation
Respuesta
  • 50%
  • 20%
  • 30%
  • 40%

Pregunta 23

Pregunta
This is the copper conductor that interconnects the TMGB to TGB
Respuesta
  • TBB
  • GE
  • TEBC
  • ACEG

Pregunta 24

Pregunta
Cross-Connect Field Colors: Network Connections
Respuesta
  • Green
  • Blue
  • Purple
  • Yellow

Pregunta 25

Pregunta
Who should the ITS installer seek guidance from for minimum safety requirements for safe work & employee health
Respuesta
  • AHJ
  • Employer
  • OHSA
  • Safety Director

Pregunta 26

Pregunta
What is the recommended maximum value for the bonding resistance between any 2 points where bonding exists
Respuesta
  • 0.1 Ohms
  • 1 Ohm
  • 10 Ohms
  • 0.01 Ohms

Pregunta 27

Pregunta
The refractive index of the fiber core is higher than that of the cladding
Respuesta
  • True
  • False

Pregunta 28

Pregunta
This type of backbone consists of cabling that is installed between a MC and IC/HC
Respuesta
  • First Level
  • Second Level
  • Interbuilding
  • Fiber Optic

Pregunta 29

Pregunta
This is a result from different optical fiber lengths in multimode fiber
Respuesta
  • Overfill Launch
  • Modal Dispersion
  • Modal Bandwidth

Pregunta 30

Pregunta
This type of protector is used to protect against sneak current
Respuesta
  • Primary
  • Secondary
  • Data & Fire Alarm
  • Carbon

Pregunta 31

Pregunta
Abandoned cable can become fuel and is a fire hazard
Respuesta
  • True
  • False

Pregunta 32

Pregunta
Cross-Connect Field Colors: First Level Backbone
Respuesta
  • White
  • Gray
  • Brown
  • Blue

Pregunta 33

Pregunta
Why is copper a preferred conductor (select all correct)
Respuesta
  • Economical
  • Offers less resitance
  • Readily available
  • Easy to produce

Pregunta 34

Pregunta
This type of protector has a reaction time of 3-5ns
Respuesta
  • Gas
  • Carbon
  • Solid State
  • Primary

Pregunta 35

Pregunta
The results of a __________ will be used to develop the project schedule and the installation job plan
Respuesta
  • Site survey
  • Scope of work
  • Specification

Pregunta 36

Pregunta
Humans can hear in what frequency range
Respuesta
  • 20-20,000Hz
  • 20-20,000MHz
  • 20-2,000Hz
  • 20-2,000MHz

Pregunta 37

Pregunta
A micrometer is
Respuesta
  • 1 billionth of a meter
  • 1 thousandth of a meter
  • 1 millionth of a meter

Pregunta 38

Pregunta
The primary responsibility of the ___________ is safeguarding personnel, property and equipment from foreign electrical voltages and current
Respuesta
  • ITS Installer
  • Qualified Electrican

Pregunta 39

Pregunta
When personnel are relocated into temporary office space during retrofits
Respuesta
  • Temporary Space
  • Swing-space Phasing
  • Project Relocation

Pregunta 40

Pregunta
When are GFCIs required (select all correct)
Respuesta
  • with temporary electrical wiring
  • extension cords
  • in Data Centers

Pregunta 41

Pregunta
What is the movement of information in the form of electrical or optical signals from one point to another through a transport medium
Respuesta
  • Transmission
  • Signal Transfer
  • Attenuation
  • Propagation Delay

Pregunta 42

Pregunta
More deaths result from flames rather than smoke and toxic gases
Respuesta
  • True
  • False

Pregunta 43

Pregunta
What does OSHA have the authority to do (select all correct)
Respuesta
  • Develop, publish & enforce safety regulations
  • Shut down unsafe job site
  • Levy fines against individuals and companies
  • confiscate tools and equipment

Pregunta 44

Pregunta
The [blank_start]T Rating[blank_end] is the amount of time in hours the firestopping system can keep the temperature from rising above a specified point
Respuesta
  • T Rating
  • F Rating
  • L Rating

Pregunta 45

Pregunta
List 3 distinct, yet interconnected grounding systems (Select all correct)
Respuesta
  • AC Grounding Electrode System
  • Equipment Grounding System
  • Telecommunications Bonding Infrastructure
  • Supplemental Ground System

Pregunta 46

Pregunta
1 cycle in 1 second = ?
Respuesta
  • 1Hz
  • 100Hz
  • 10Hz
  • 1MHz

Pregunta 47

Pregunta
Which fiber is most common for backbone & horizontal runs within buildings and campus environments
Respuesta
  • Multimode
  • Singlemode
  • OM2
  • OM1

Pregunta 48

Pregunta
If expanding a TR, what must be done prior to removing the wall with equipment/hardware
Respuesta
  • Float the backboard
  • Hang the backboard
  • temporarily support the backboard

Pregunta 49

Pregunta
What type of ladder is not allowed to be used by an ITS installer
Respuesta
  • Aluminum
  • Wood
  • Extension
  • Fiberglass

Pregunta 50

Pregunta
What is the diameter of the cladding in multimode fiber cable
Respuesta
  • 50um
  • 125um
  • 62.5um
  • 250um

Pregunta 51

Pregunta
What is the distance limitation of multimode fiber
Respuesta
  • 2,000 meters
  • 3,000 meters
  • 1,000 meters
  • 10,000 meters

Pregunta 52

Pregunta
If an extension ladder is extended 24ft up, then how far should the base be out
Respuesta
  • 5ft
  • 4ft
  • 6ft
  • 8ft

Pregunta 53

Pregunta
Which transmission method transmits a signal in one direction only
Respuesta
  • Simplex
  • Full Duplex
  • Half Duplex

Pregunta 54

Pregunta
It is acceptable to use a TE in place of a TR
Respuesta
  • True
  • False

Pregunta 55

Pregunta
Which fiber supports wavelengths of 1310nm, 1490nm, 1550nm & 1625nm
Respuesta
  • Singlemode
  • Multimode

Pregunta 56

Pregunta
What is the minimum size of stub up conduits
Respuesta
  • 3/4"
  • 1/2"
  • 1"
  • 7/8"

Pregunta 57

Pregunta
How many rungs need to overlap when extending an extension ladder
Respuesta
  • 3
  • 2
  • 4
  • 5

Pregunta 58

Pregunta
What is the measure of analog signal strength
Respuesta
  • Bit
  • Bel
  • Volt
  • Watt

Pregunta 59

Pregunta
How far should an extension ladder extend above a work area
Respuesta
  • 3ft
  • 2ft
  • 4ft
  • 3m

Pregunta 60

Pregunta
This current will trigger ventricular fibrillation, which causes the heart to repeatedly relax and violently clamp shut (usually results in death)
Respuesta
  • 100mA
  • 200mA
  • 50mA
  • 50-100mA

Pregunta 61

Pregunta
One of the primary functions of the ____________ is to house the floor-serving cross-connections and interconnection
Respuesta
  • TR
  • ER
  • TE
  • EF

Pregunta 62

Pregunta
What is the distance limitation of singlemode fiber
Respuesta
  • 2,000 meters
  • 3,000 meters
  • 5,000 meters
  • 10,000 meters

Pregunta 63

Pregunta
___________ are not dependent on ITS installers
Respuesta
  • Customers
  • Employees
  • IT Professionals

Pregunta 64

Pregunta
How far must an ITS installer stay away from exposed energized circuits operating at 300-50,000 volts
Respuesta
  • 10ft
  • 12ft
  • 6ft
  • 8ft

Pregunta 65

Pregunta
Which fiber supports wavelengths of 850nm and 1300nm
Respuesta
  • Multimode
  • Singlemode

Pregunta 66

Pregunta
What the 3 distinct ways in which others perceive and employee (select all correct)
Respuesta
  • Body language
  • Tone of voice
  • Choice of words
  • Facial expressions

Pregunta 67

Pregunta
Chin straps are not allowed to be used with hardhats
Respuesta
  • True
  • False

Pregunta 68

Pregunta
What is the most common fire protection principle
Respuesta
  • Compartmentation
  • Suppression
  • Detection

Pregunta 69

Pregunta
Which fiber generally uses LED and VCSEL light sources
Respuesta
  • Multimode
  • Singlemode

Pregunta 70

Pregunta
What is the diameter of the acrylate coating in fiber cable
Respuesta
  • 50um
  • 125um
  • 250um
  • 100um

Pregunta 71

Pregunta
What is the typical lifespan of a hard hat
Respuesta
  • 5 years
  • 1 year
  • 3 years
  • 2 years

Pregunta 72

Pregunta
What is the most common tight buffer diameter
Respuesta
  • 900um
  • 250um
  • 3mm

Pregunta 73

Pregunta
Tone of voice is ____% of communication perceptions
Respuesta
  • 7%
  • 38%
  • 55%

Pregunta 74

Pregunta
If using a MUTOA, what is the maximum length of a 24AWG, stranded work area cable if the horizontal cable is 70 meters
Respuesta
  • 22 meters
  • 25 meters
  • 5 meters
  • 27 meters

Pregunta 75

Pregunta
Which method transmits in either direction but in only 1 direction at a time
Respuesta
  • Simplex
  • Half duplex
  • Full duplex

Pregunta 76

Pregunta
Stickers are allowed to be placed on hard hats
Respuesta
  • True
  • False

Pregunta 77

Pregunta
Tight buffer fiber is only installed in multimode fiber
Respuesta
  • True
  • False

Pregunta 78

Pregunta
What is the maximum amount of moisture allowed in plywood backboards
Respuesta
  • 15%
  • 20%
  • 5%
  • 10%

Pregunta 79

Pregunta
Which type of fiber requires a furcation kit
Respuesta
  • Tight Buffer
  • Multimode
  • Loose Tube
  • Singlemode

Pregunta 80

Pregunta
Select all approved eye protection
Respuesta
  • Glasses
  • Goggles
  • Full Face Shield

Pregunta 81

Pregunta
This type of fiber consists of up to 24 strands bundled together in a single line that is color coded
Respuesta
  • Ribbon
  • Air blown
  • Tight buffer
  • Loose tube

Pregunta 82

Pregunta
These are to be installed on exposed circuits as near as possible to the point at which the exposed cables enter the bulding
Respuesta
  • Primary Protection
  • Secondary Protection
  • Data & Fire Alarm Protector

Pregunta 83

Pregunta
This firestop product is intumescent, metal back and used to seal large openings
Respuesta
  • sheets
  • putty
  • blankets
  • pads

Pregunta 84

Pregunta
This firestop material is a putty that is used to seal the back of outlet boxes
Respuesta
  • pads
  • sheets
  • wrap strips

Pregunta 85

Pregunta
This firestop material is intumescent used for plastic piping, insulated metal piping or cable bundles
Respuesta
  • wrap strips
  • putty
  • caulk

Pregunta 86

Pregunta
This firestop material is intumescent but mostly endothermic, soft and pliable. It comes in bars and sticks
Respuesta
  • putty
  • pads
  • foams

Pregunta 87

Pregunta
This firestop material can be intumescent, endothermic or ablative. It comes in tubes and can up to 2 weeks to to cure. It is used for permanent installations
Respuesta
  • caulk
  • putty
  • pillows

Pregunta 88

Pregunta
This firestop material is regarded as temporary and requires wire restraints to pass the hose test
Respuesta
  • pillows
  • putty
  • caulk

Pregunta 89

Pregunta
This firestop material incorporates putty and is referred to as a pipe choke system
Respuesta
  • collars
  • putty
  • foam

Pregunta 90

Pregunta
This firestop material may be intumescent, endothermic or ablative. It is a 2 part mixing with fast curing time
Respuesta
  • foam
  • sheets
  • blankets

Pregunta 91

Pregunta
Select the 3 types of centralized fiber cabling implementations
Respuesta
  • Pull-through
  • Interconnection
  • Splice in the TR
  • Home Run

Pregunta 92

Pregunta
This is a property of an electrical force field built around a conductor that opposes and changes in current flow in a circuit
Respuesta
  • Inductance
  • Capacitance
  • Resistance
  • Impedance

Pregunta 93

Pregunta
Words are _____% of communication perceptions
Respuesta
  • 7%
  • 38%
  • 55%

Pregunta 94

Pregunta
Air-blown systems are designed & manufactured for an expected operating lifetime of how many years
Respuesta
  • 20
  • 30
  • 10
  • 15

Pregunta 95

Pregunta
What refers to the amount of information that can be transported over the media
Respuesta
  • Megahertz
  • Megabit
  • Decibel

Pregunta 96

Pregunta
This current causes the heart the clamp shut and severe burns occur on the skin and hair
Respuesta
  • 100mA
  • 200mA
  • 50-100mA
  • 50mA

Pregunta 97

Pregunta
An ITS installer is allowed to leave a personnel lift with a safety belt with a non-locking keeper
Respuesta
  • True
  • False

Pregunta 98

Pregunta
Increasing the length of fiber or wavelength of the light source will decrease bandwidth
Respuesta
  • True
  • False

Pregunta 99

Pregunta
Open top cable supports are typically intended to support how many cables
Respuesta
  • 50
  • 20
  • 30
  • 40

Pregunta 100

Pregunta
Cross-Connect Field Colors: Miscellaneous
Respuesta
  • Yellow
  • Blue
  • Purple
  • Green

Pregunta 101

Pregunta
What is the basic unit of inductance
Respuesta
  • Henry
  • Watt
  • Farad
  • Ohm

Pregunta 102

Pregunta
There is no mandatory standard to identify the color coding for fiber
Respuesta
  • True
  • False

Pregunta 103

Pregunta
This firestop material is used in situations where a cable tray containing critical power or data cables must remain in operation during a fire
Respuesta
  • Blankets
  • Sprays
  • Pillows
  • Putties

Pregunta 104

Pregunta
According to standards, horizontal fiber cable is normally ____________
Respuesta
  • Multimode
  • Singlemode
  • Tight buffer
  • Loose tube

Pregunta 105

Pregunta
What is the minimum bend radius of a fiber cable, with up to 4 strands, during installation
Respuesta
  • 1 inch
  • 2 inch
  • 4 x diameter of cable
  • 10 x diameter of cable

Pregunta 106

Pregunta
What is the minimum bend radius of a fiber cable, with up to 4 strands, at rest
Respuesta
  • 1 inch
  • 2 inch
  • 4 x diameter of cable
  • 10 x diameter of cable

Pregunta 107

Pregunta
What is the minimum bend radius of interbuilding fiber during installation
Respuesta
  • 10 x diameter of cable
  • 15 x diameter of cable
  • 20 x diameter of cable

Pregunta 108

Pregunta
What is the minimum bend radius of a fiber backbone cable at rest
Respuesta
  • 15 x diameter
  • 10 x diameter
  • 20 x diameter

Pregunta 109

Pregunta
What is the minimum bend radius of an intrabuilding fiber during installation
Respuesta
  • 10 x diameter
  • 15 x diameter
  • 20 x diameter

Pregunta 110

Pregunta
Which test instruments can be used to test fiber while it is still on the reel (select all correct)
Respuesta
  • OLTS
  • VFL
  • OTDR

Pregunta 111

Pregunta
Which fiber test instrument does not require access to both ends of the fiber while testing on the reel
Respuesta
  • VFL
  • OTDR
  • OLTS

Pregunta 112

Pregunta
Bonding conductors are designed to intentionally carry AC ground fault current or lightning strike current
Respuesta
  • True
  • False

Pregunta 113

Pregunta
What is the maximum length for horizontal fiber runs
Respuesta
  • 90 meters
  • 100 meters
  • 2,000 meters
  • 3,000 meters

Pregunta 114

Pregunta
Lift belts give the user added strength
Respuesta
  • True
  • False

Pregunta 115

Pregunta
This administration addresses infrastructure with multiple buildings at a single site
Respuesta
  • Class 1
  • Class 2
  • Class 3
  • Class 4

Pregunta 116

Pregunta
It is recommended to order innerduct without a pull sting preisntalled
Respuesta
  • True
  • False

Pregunta 117

Pregunta
Select all approved types of hearing protection
Respuesta
  • Aural
  • Foam Earplugs (disposable)
  • Rubber Earplugs (reusable)

Pregunta 118

Pregunta
This type of protector has a reaction time of 15ns or more
Respuesta
  • Gas tubes
  • Solid state
  • Carbon blocks

Pregunta 119

Pregunta
This is the property of conductors that allows storage of electric charges when potential differences exist between conductors
Respuesta
  • Capacitance
  • Inductance
  • Resistance
  • Impedance

Pregunta 120

Pregunta
Body language is ______% of communication perceptions
Respuesta
  • 7%
  • 38%
  • 55%

Pregunta 121

Pregunta
This firestop material will develop a hard char that resists erosion from fire and flames
Respuesta
  • Ablative
  • Intumescent
  • Endothermic

Pregunta 122

Pregunta
This administration addresses infrastructure with one or more telecommunication spaces in a single building
Respuesta
  • Class 1
  • Class 2
  • Class 3
  • Class 4

Pregunta 123

Pregunta
Fall protection is required at which height
Respuesta
  • 4ft
  • 5ft
  • 3ft
  • 6ft

Pregunta 124

Pregunta
Which is the required physical topology for SCS
Respuesta
  • Star
  • Ring
  • Bus

Pregunta 125

Pregunta
(2) 1.5 inch and (1) 1 inch innerducts are recommended to be placed inside what size conduit
Respuesta
  • 3 inch
  • 2 inch
  • 4 inch
  • 6 inch

Pregunta 126

Pregunta
Cross-Connect Field Colors: Horizontal Cable
Respuesta
  • Blue
  • Green
  • Yellow
  • Orange

Pregunta 127

Pregunta
A PFAS (personal fall arrest system) includes a full body harness, a shock absorbing lanyard & secure anchorage point capable of supporting ______ pounds
Respuesta
  • 2,500lbs
  • 5,000lbs
  • 3,000lbs
  • 1,000lbs

Pregunta 128

Pregunta
The service loop is used to relieve all tension of the fiber cable
Respuesta
  • True
  • False

Pregunta 129

Pregunta
What is allowed to be used to mend torn clothing
Respuesta
  • duct tape
  • electrical tape
  • tie wraps

Pregunta 130

Pregunta
How much horizontal fiber should be left at the work area
Respuesta
  • 1 meter
  • 2 feet
  • 18 inches
  • 12 inches

Pregunta 131

Pregunta
How much fiber slack should be left in a cabinet within a TR
Respuesta
  • 10 meters
  • 3 feet
  • 1 meter
  • 3 meters

Pregunta 132

Pregunta
Capacitance is measured in ________
Respuesta
  • Farads
  • Henry
  • Ohm
  • Watts

Pregunta 133

Pregunta
Plywood backboards should be mounted at _____ AFF
Respuesta
  • 8 inches
  • 12 inches
  • 6 inches
  • 18 inches

Pregunta 134

Pregunta
This current will produce a tingling of the skin
Respuesta
  • 2-3mA
  • 10mA
  • 50-100mA
  • 50mA

Pregunta 135

Pregunta
When blowing fiber, what carries the cable down the tube
Respuesta
  • fluid drag
  • air pressure
  • vacuum

Pregunta 136

Pregunta
What describes the amount of information a fiber is capable of transporting
Respuesta
  • Modal Bandwidth
  • Dispersion
  • Megahertz

Pregunta 137

Pregunta
Which method transmits a signal in both directions at the same time
Respuesta
  • Full duplex
  • Half duplex
  • Simplex

Pregunta 138

Pregunta
What type of entrance pathway preserves the aesthetic appearance of the building and is economical over the life cycle
Respuesta
  • Underground
  • Buried
  • Aerial
  • Wireless

Pregunta 139

Pregunta
Air blown fiber shall not be used for outside plant
Respuesta
  • True
  • False

Pregunta 140

Pregunta
This administration addresses infrastructure with multiple sites or campuses
Respuesta
  • Class 1
  • Class 2
  • Class 3
  • Class 4

Pregunta 141

Pregunta
This current will produce a painful shock and muscles can't release the contact
Respuesta
  • 10mA
  • 2-3mA
  • 50mA
  • 100mA

Pregunta 142

Pregunta
Which of the following are basic tests to verify each tube prior to blowing fiber (select all correct)
Respuesta
  • airflow testing
  • pressure testing
  • continuity testing

Pregunta 143

Pregunta
This is required on every 3rd floor and top floor of a multi-story building that has multiple ER/TRs on the same floor
Respuesta
  • GE
  • TGB
  • TEBC
  • GEC

Pregunta 144

Pregunta
This serves as the dedicated extension of the building AC grounding electrode system of the telecommunications infrastructure
Respuesta
  • TMGB
  • TGB
  • GEC
  • ACEG

Pregunta 145

Pregunta
What is the typical air pressure when blowing fiber
Respuesta
  • 150-220psi
  • 150-200psi
  • 100-150psi
  • 200-225psi

Pregunta 146

Pregunta
Which splicing method has a low consumable cost
Respuesta
  • fusion
  • mechanical

Pregunta 147

Pregunta
What is the total opposition to current flow
Respuesta
  • Impedance
  • Capacitance
  • Resistance
  • Inductance

Pregunta 148

Pregunta
What is the basic unit of digital information
Respuesta
  • bit
  • megabit
  • bel

Pregunta 149

Pregunta
What type of entrance pathway preserves the aesthetic appearance of the building but is inflexible for future service changes
Respuesta
  • tunnel
  • underground
  • buried
  • aerial

Pregunta 150

Pregunta
What diameter of toggle bolts should be used when mounting a backboard
Respuesta
  • 1/4"
  • 3/8"
  • 1/2"
  • 5/8"

Pregunta 151

Pregunta
Open top cable supports should be installed to maintain a minimum of _____ inches above ceilings
Respuesta
  • 2
  • 3
  • 4
  • 5

Pregunta 152

Pregunta
Reflectance may be a concern with which type of splicing method
Respuesta
  • fusion
  • mechanical

Pregunta 153

Pregunta
This administration addresses the needs of premises served by a single ER (the only telecommunication space)
Respuesta
  • Class 1
  • Class 2
  • Class 3
  • Class 4

Pregunta 154

Pregunta
How much fiber typically should be in a splice tray
Respuesta
  • 3 feet
  • 1-2 meters
  • 1-3 meters
  • 1 meter

Pregunta 155

Pregunta
Identify this fusion
Respuesta
  • fuse time too long
  • autofeed too low
  • autofeed too high
  • fuse current too hot

Pregunta 156

Pregunta
Identify this fusion
Respuesta
  • fuse current too hot
  • autofeed too high
  • good splice
  • autofeed too low

Pregunta 157

Pregunta
Identify this fusion
Respuesta
  • autofeed too high
  • good splice
  • fuse time too long
  • fuse current too hot

Pregunta 158

Pregunta
Identify this fusion
Respuesta
  • autofeed too low
  • fuse time too long
  • autofeed too high
  • good splice

Pregunta 159

Pregunta
Identify this fusion
Respuesta
  • good splice
  • autofeed too high
  • autofeed too low
  • fuse time too long

Pregunta 160

Pregunta
What is the maximum splice loss regardless of the methodology
Respuesta
  • .3dB
  • .1dB
  • .75dB
  • 1.5dB

Pregunta 161

Pregunta
What is the curing cycle for heat cured connectors
Respuesta
  • 20 minutes
  • 10 minutes
  • 5 minutes
  • 15 minutes

Pregunta 162

Pregunta
24AWG stranded cable ha _______ more attenuation
Respuesta
  • 30%
  • 20%
  • 50%
  • 40%

Pregunta 163

Pregunta
Adhesive hardening when terminating anaerobic connectors takes how long
Respuesta
  • 10-20 seconds
  • 15 seconds
  • 1 minute
  • 5-10 seconds

Pregunta 164

Pregunta
True power is measured in ______
Respuesta
  • Watts
  • Volts
  • Amps
  • Decibels

Pregunta 165

Pregunta
What is the size of the primary acrylate
Respuesta
  • 125um
  • 250um
  • 245um
  • 5um

Pregunta 166

Pregunta
Measure of signal loss resulting from the insertion of component, link or channel between transmitter and receiver (often referred to as attenuation)
Respuesta
  • Crosstalk
  • Return loss
  • Delay skew
  • Insertion loss

Pregunta 167

Pregunta
How far should the toggle bolts be spaced when mounting a backboard
Respuesta
  • 1ft
  • 2ft
  • 18 inches
  • 3ft

Pregunta 168

Pregunta
All electrical activity produces electric & magnetic fields
Respuesta
  • True
  • False

Pregunta 169

Pregunta
What quantifies the bandwidth of a cabling system in a frequency range
Respuesta
  • megahertz
  • megabit
  • decibel

Pregunta 170

Pregunta
What is the #1 reason for troubleshooting in optical networks
Respuesta
  • contamination
  • core alignment
  • poor terminations

Pregunta 171

Pregunta
What device converts a digital signal into 2 distinctive analog frequencies
Respuesta
  • modem
  • codec

Pregunta 172

Pregunta
What is the power range for microscopes to view the end face of an optical fiber connector
Respuesta
  • 100x-800x
  • 100x-200x
  • 200x-400x

Pregunta 173

Pregunta
What is the ratio expressed in decibels of the power of the outgoing signal to the power of the reflected signal
Respuesta
  • Return loss
  • Insertion loss
  • Crosstalk
  • Delay skew

Pregunta 174

Pregunta
This is the grounding connection point for telecommunications systems and equipment in the area served by an ER or TR
Respuesta
  • GEC
  • TGB
  • TMGB
  • BCT

Pregunta 175

Pregunta
The inside bend radius shall be _______ times the ID for conduits 2 inches or less
Respuesta
  • 6
  • 10
  • 4
  • 8

Pregunta 176

Pregunta
This tool is used to inspect the radius of curvature, offset of polish & optical fiber height
Respuesta
  • VFL
  • Interferometer
  • OLTS
  • OTDR

Pregunta 177

Pregunta
This is the copper conductor that interconnects the TMGB to TGB
Respuesta
  • TBB
  • GEC
  • GE
  • ACEG

Pregunta 178

Pregunta
This is the unwanted transfer of a signal's EM energy from one or more circuits to other circuits
Respuesta
  • Crosstalk
  • Delay Skew
  • Return Loss
  • Insertion Loss

Pregunta 179

Pregunta
This tool can determine end-to-end attenuation & distance to a point of high attenuation during pre-installation testing
Respuesta
  • OTDR
  • OLTS
  • VFL
  • Interferometer

Pregunta 180

Pregunta
Test equipment uses what to determine the length of a cable
Respuesta
  • Crosstalk
  • NVP (nominal velocity of propagation)
  • Insertion Loss
  • Propagation Delay

Pregunta 181

Pregunta
How far does the conductor need to extend beyond the connector if using a set-screw, pass-through style lug
Respuesta
  • 1/8"
  • 1/4"
  • 1/2"
  • 3/8"

Pregunta 182

Pregunta
Cross-Connect Field Colors: Common Equipment
Respuesta
  • Purple
  • Green
  • Yellow
  • Red

Pregunta 183

Pregunta
What device converts analog data, from a video device, to a digital signal
Respuesta
  • modem
  • codec

Pregunta 184

Pregunta
The inside bend radius shall be ___ times the ID for conduits greater than 2 inches
Respuesta
  • 10
  • 6
  • 4
  • 8

Pregunta 185

Pregunta
Acceptance testing of optical fiber is most often performed with which tester
Respuesta
  • VFL
  • OLTS
  • OTDR
  • Interferometer

Pregunta 186

Pregunta
What are unsafe oxygen levels
Respuesta
  • below 19.5% and above 23.5%
  • below 20.5% and above 25.5%
  • below 15.5% and above 20.5%

Pregunta 187

Pregunta
Time for a signal to be transmitted from one end to the other
Respuesta
  • Crosstalk
  • Delay Skew
  • Propagation Delay
  • Insertion Loss

Pregunta 188

Pregunta
Which entrance pathway has the lowest cabling installation cost
Respuesta
  • Aerial
  • Underground
  • Buried
  • Wireless

Pregunta 189

Pregunta
For singlemode fiber, out-of-band testing may be accomplished at the _____ nm window
Respuesta
  • 1625
  • 1550
  • 1310
  • 1490

Pregunta 190

Pregunta
Difference in propagation delay between slowest & fastest pairs within same cable sheath
Respuesta
  • delay skew
  • crosstalk
  • insertion loss
  • return loss

Pregunta 191

Pregunta
What is the worst acceptable loss for a mated pair
Respuesta
  • .75dB
  • .5dB
  • .3dB
  • 1.0dB

Pregunta 192

Pregunta
95% of mated pairs shall be better than ____dB loss
Respuesta
  • .75dB
  • .5dB
  • .3dB

Pregunta 193

Pregunta
This type of protector has a reaction time of 10-15 ns
Respuesta
  • Gas
  • Carbon
  • Solid state
  • Fire & data

Pregunta 194

Pregunta
There is currently no maximum bandwidth for singlemode optical fiber
Respuesta
  • True
  • False

Pregunta 195

Pregunta
This firestop material expands when exposed to fire or heat
Respuesta
  • intumescent
  • ablative
  • endothermic

Pregunta 196

Pregunta
This backbone cable distributes telecommunications services between buildings
Respuesta
  • interbuilding
  • intrabuilding

Pregunta 197

Pregunta
Cross-Connect Field Colors: Demarcation Point
Respuesta
  • Orange
  • Brown
  • White
  • Red

Pregunta 198

Pregunta
What is the maximum amount of exposure between the insulation and the bonding connector
Respuesta
  • 1/8"
  • 1/2"
  • 1/4"
  • 3/8"

Pregunta 199

Pregunta
What can be used to neutralize small acid spills
Respuesta
  • sodium bicarbonate
  • water
  • milk
Mostrar resumen completo Ocultar resumen completo

Similar

Chapter 5 Copper
eric rinehart
Telecomms Rigging
peter.roberts
Banderas
Diego Santos
Rol del profesor y del estudiante dentro del aprendizaje
Rita Serrano
Mapas Mentales
Celia Sanchez
Ácidos, bases y sales - Formulación y nomenclatura
pedro.casullo
LA INDEPENDENCIA DE ESTADOS UNIDOS
ROSA MARIA ARRIAGA
Las Alteraciones
mariajesus camino
Mapa mental inteligencia emocional
Alexandra A
Mesoamerica- Linea del tiempo
jonyjr1