NCCER 26206-14 Conductor Installations - Quiz 2

hcannaday 6 preguntas

Hacer el test

Preguntas del test (6)

  1. 1The ends of 1,000 kcmil conductors can be trimmed using _____.
    1. Acable cutters
    2. Bscissors
    3. Ca cable reamer
    4. Dpliers
  2. 2The three types of fish tape are steel, nylon, and _____.
    1. Afiberglass
    2. Bcotton
    3. Ccopper
    4. Dhemp
  3. 3Which of the following is one of the most common types of wire-pulling rope on the market today?
    1. ASisal
    2. BHemp
    3. CCopper
    4. DNylon
  4. 4In general, the maximum sidewall load on any raceway run should be _____.
    1. A100 pounds/foot of bend
    2. B200 pounds/foot of bend
    3. C350 pounds/foot of bend
    4. D500 pounds/foot of bend
  5. 5What is the maximum length of cable weighing 5 lbs/ft that can be pulled through a 45-degree bend with a
    coefficient of friction of 1.48 using equipment with a maximum pulling force of 2,000 pounds?
    1. A40
    2. B270
    3. C308
    4. D1,351
  6. 6Which of the following devices is designed to read pulling force during a cable pull?
    1. ACircuit tester
    2. BDynamometer
    3. CCable length meter
    4. DWire sorter