Gas safety

Description

Flashcards on Gas safety, created by pjc9803 on 24/08/2015.
pjc9803
Flashcards by pjc9803, updated more than 1 year ago
pjc9803
Created by pjc9803 over 8 years ago
20
2

Resource summary

Question Answer
GSIUR 1998 reg 26 (9) (9) Where a person performs work on a gas appliance he shall immediately thereafter examine – (a) the effectiveness of any flue; (b) the supply of combustion air; (c) its operating pressure or heat input or, where necessary, both; (d) its operation so as to ensure its safe functioning, and forthwith take all reasonably practicable steps to notify any defect to the responsible person and, where different, the owner of the premises in which the appliance is situated or, where neither is reasonably practicable, in the case of an appliance supplied with liquefied petroleum gas, the supplier of gas to the appliance, or, in any other case, the transporter.
GSIUR 1998 reg 34(3) 3) Any person engaged in carrying out any work in relation to a gas main, service pipe, service pipework, gas storage vessel or gas fitting who knows or has reason to suspect that any gas appliance cannot be used without constituting a danger to any person shall forthwith take all reasonably practicable steps to inform the responsible person for the premises in which the appliance is situated and, where different, the owner of the appliance or, where neither is reasonably practicable, in the case of an appliance supplied with liquefied petroleum gas, the supplier of gas to the appliance, or, in any other case, the transporter.
GSIUR 1998 reg 34(4) (4) In paragraph (3) above, the expression “work” shall be construed as if, in the definition of “work” in regulation 2(1) above, every reference to a gas fitting were a reference to a gas main, service pipe, service pipework, gas storage vessel or gas fitting.
RIDDOR Reporting Within 14 days or 2 hrs if death or hospitalisation occurs.
Gas tightness test visual inspection Appliances off, pilots extinguished Cooker lid open ECV turned off Remove test nipple Attach zeroed manometer Let by 10mbar for 1 min (0.25mbar) 20mbar -1min stabilisation Tightness 20mbar for 2 mins
Gas tightness- permitted drops 28mm -35mm E6. 8mbar - 4.5mbar U6/G4. 4mbar - 2.5mbar U16/G10. 1mbar - 1mbar
Purge procedure Meter G10/ U16 up to 35mm calculation required Meter E6,G4 or U6 up to 28mm- 0.01m3 (0.35ft3 for U6 meter) Advise customer- open doors and windows- note meter reading- purge furthest point- test joint for tightness- check appliances burning correctly
Operating pressure at meter Between 19 and 21mbar- no more than 1mbar drop over installation
Gas rating E6 / G4 Full rate for 2 mins- x30 for hourly consumption (m3/hr) - covert to cubic feet x 35.31-convert to btus x 1040- convert to kW devide by 3412- devide by 1.11 for (net) kW
Gas rating for U6 meter Full rev in seconds-3600 divide by seconds=ft3/hr-convert to btus x 1040- divide by 3412 for kW - devide by 1.11 for (net) kW
Work In relation to a gas fitting, this includes any of the following activities carried out by any person, whether an employee or not: a) Installing or reconnecting the fitting; b) Maintaining, servicing, disconnecting, permanently adjusting, repairing, altering or renewing the fitting or purging it of air or gas; c) Where the fitting is not readily movable, changing its position; and d) Removing the fitting. Note: Work in this context does not include the connection or disconnection of a bayonet fitting or other self-sealing connector.
Trigger points (interruption) location > Flueing > Ventilation > Signs of distress > stable and secure > Flame picture
Additional ECV Meter more than 6m from dwelling
Pipe supports copper 15mm vertical 2m horizontal 1.5m 22mm or above vertical 2.5m horizontal 2.0m
GSIUR 1998 covers responsibilities of people including those: Installing, servicing, maintaining or repairing gas appliances and other gas fittings. as well as: suppliers and users of gas and certain landlords
Pipe sizing Remember- max pressure loss of 1mbar divide 1mbar by number of sections total pipe length including fitting (0.5m for each elbow or tee. 0.3m for 90deg bend) x number of sections
Show full summary Hide full summary

Similar

Safety Legislation
Katie Shellard
Blood Brothers (Characters)
nuhaheza
Causes of the Cold War Quiz
Fro Ninja
To Kill A Mockingbird Complete Notes
jessica.moscrip
Bayonet Charge flashcards
katiehumphrey
The Digestive system
Elena Cade
Japanese Hiragana
pangcaberte
Photosynthesis and Respiration
Jessica Phillips
2_PSBD HIDDEN QUS By amajad ali
Ps Test
1PR101 2.test - Část 11.
Nikola Truong
1PR101 2.test - Část 19.
Nikola Truong