Question 1
Question
Schedule 80 pipe is required in a propane system:
Answer
-
for propane vapour under 125 psig (860 kPa) working pressure
-
when steel piping is to be connected to plastic piping
-
for propane vapour over 125 psig (860 kPa) working pressure
-
when copper piping is to be connected to plastic pipe
Question 2
Question
When sizing branch line, what is the maximum size a job fabricated welded fitting that can be used in a 6” NPS gas supply
Answer
-
6” NPS
-
3” NPS
-
4” NPS
-
2” NPS
Question 3
Question
Natural gas piping in industrial buildings shall be identified:
Answer
-
with yellow paint or yellow bands
-
with red paint or red bands
-
with paint in a contrasting colour to other pipes
-
with green paint and yellow bands
Question 4
Question
A panel-mounted ground fault circuit interrupting breaker protects all:
Answer
-
electrical loads in the circuits from that panel
-
loads in the circuit served by that breaker
-
240 volt circuits served by that breaker panel
-
120 volt circuits served by that breaker panel
Question 5
Question
Branch circuit fuse size is determined by the:
Question 6
Question
The 24 volt control circuit supply for a residential gas furnace comes from a:
Answer
-
60/24 volt step down transformer
-
120/24 volt step down transformer
-
240/24 step down transformer
-
240/120 volt step down transformer
Question 7
Question
On an electrical schematic diagram, the safety controls are typically drawn:
Question 8
Question
The power supply to a residential gas furnace is:
Answer
-
120/1/60
-
120/2/60
-
240/1/60
-
240/2/60
Question 9
Question
As gauge number of a conductor increase, its current carrying capacity:
Answer
-
increases
-
decreases
-
remains the same
-
varies directly
Question 10
Question
As more circuits are added to a panel, the total current drawn from the panel:
Answer
-
Increases
-
decreases
-
remains the same
-
fluctuates
Question 11
Question
A hard, sharp pilot flame indicates
Question 12
Question
Direct current travels:
Question 13
Question
A receptacle-mounted ground fault interrupter protects against:
Answer
-
appliance overload
-
dead shorts
-
short circuits
-
current flow to ground
Question 14
Question
On an electrical schematic, the system is shown with the:
Answer
-
disconnect closed with all devices as though the heating is on
-
disconnect closed with all devices as though there is a call for heating but the heating has not yet come on
-
disconnect open with all devices as though there is a call for heating
-
disconnect open with all devices as though there is no call for heating
Question 15
Question
The normal fuse size for #12 AWG copper wire is:
Answer
-
15 amps
-
20 amps
-
30 amps
-
40 amps
Question 16
Question
A zero ohmmeter reading taken between the casing of a solenoid and a disconnected wire to the solenoid indicates that:
Question 17
Question
As the diameter of a conductor decreases, its resistance:
Answer
-
Increases
-
decreases
-
remains the same
-
varies directly
Question 18
Question
When can an on/off switch be installed in the neutral wire from an electrical panel to a gas furnace:
Answer
-
never
-
only when it carries 24 volts or less
-
only when the switch is 3 feet or less from the appliance
-
only when the supply is 240 volts
Question 19
Question
A thermostat with a single mercury bulb which controls a single stage heat, single stage cool unit is a ___________ control:
Answer
-
SPST (single pole single throw)
-
SPDT (single pole double throw)
-
DPST (single pole single throw)
-
DPDT (double pole double throw)
Question 20
Question
How tight should a thermocouple connection be:
Question 21
Question
What happens to the resistance inside an infrared scanner when the scanner is exposed to infrared radiation:
Question 22
Question
What is required combustion air inlet size for a stationary gas engine having an input of 1,800,000 Btuh installed in a room?
Answer
-
30 square inches (1,800 mm2)
-
60 square inches (3,900 mm2)
-
120 square inches (7,800 mm2)
-
180 square inches (11,600 mm2)
Question 23
Question
After correctly sizing an air intake opening, the grill or screen should cover the opening.
What is the minimum size of the mesh on an air intake grill?
Answer
-
3/32” (2 mm)
-
1/8” (3 mm)
-
1/4” (6 mm)
-
1/2" (12 mm)
Question 24
Question
The most important element required for proper combustion in a gas appliance is:
Answer
-
carbon dioxide
-
air
-
nitrogen
-
water vapour
Question 25
Question
The best method of removing dust from a house is:
Answer
-
humidification
-
infiltration
-
filtration
-
exfiltration
Question 26
Question
To reduce heat loss, the most effective thing to do is to:
Question 27
Question
The best way to remove odours from a house is to:
Answer
-
filter the air in the house
-
ventilate the house
-
install mechanical attic ventilation
-
humidify the air in the house
Question 28
Question
The maximum negative building pressure that a natural draft vented appliance should be exposed to is:
Answer
-
5 Pa (- 0.02” w.c.)
-
10 Pa (- 0.04” w.c.)
-
15 Pa (- 0.06” w.c.)
-
20 Pa (- 0.08” w.c.)
Question 29
Question
After a direct vent radiant heating system is installed in a new house, the customer complains that, “The walls and windows are wet.” From the following list, what is the most reasonable response?
Answer
-
after confirming the heat exchanger is not cracked, advise the customer to call for someone else
-
recommend that a window be left open a bit
-
advise the customer that the problem will disappear when the building dries out
-
recommend the installation of a mechanical ventilation system
Question 30
Question
Indoors in winter, if a vapour barrier has not been made continuous, the:
Question 31
Question
From the following list, which action will have the greatest effect on reducing mold growth in the house?
Answer
-
reducing relative humidity to approximately 10%
-
increasing relative humidity to approximately 80%
-
filtering the air in the house
-
covering earthen floors and open water surfaces
Question 32
Question
Which of the following actions will limit the problems caused by the “distribution effect” on conventional vented forced air furnaces?
Answer
-
seal the ductwork in the furnace area
-
balance the volume of return and supply air in each room or floor
-
ensure a tight seal around the furnace filter and blower door
-
all of the available choices
Question 33
Question
Currently, the most common type of building construction is:
Answer
-
balloon
-
platform
-
double brick
-
solid brick
Question 34
Question
The main purpose of the building skin is to:
Answer
-
protect the underlying materials
-
reduce heat gain
-
improve resistance to vapour flow
-
maintain the depressurization limit
Question 35
Question
The “systems approach” as it applies to a building is a means of understanding how fuel-fired appliances affect and are affected by the:
Question 36
Question
Which symbol represents a gas solenoid?
Question 37
Question
Which symbol represents the dryer heat thermostat?
Question 38
Question
Which symbol represents a dryer high limit switch?
Question 39
Question
Which symbol represents a dryer centrifugal switch?
Question 40
Question
Which symbol represents a dryer pilot switch?
Question 41
Question
Which symbol represents a timer motor?
Question 42
Question
The required clearance to combustible material above a pendant gas lamp is:
Answer
-
5 inches (125 mm)
-
12 inches (300 mm)
-
15 inches (375 mm)
-
18 inches (450 mm)
Question 43
Question
The mantle of a gas lamp:
Question 44
Question
What is the minimum clearance from the sides of a domestic range to combustible materials, unless otherwise specified?
Answer
-
1 inches (25 mm)
-
3 inches (75 mm)
-
6 inches (150 mm)
-
9 inches (225 mm)
Question 45
Question
What type of protection does a range require if it is certified for zero side clearance from combustible material?
Answer
-
28 MSG (0.3 mm) sheet metal spaced out 0.25 inch (6 mm)
-
28 MSG (0.3 mm) sheet metal applied directly to the combustible material
-
1/4 inch (6 mm) asbestos millboard
-
no protection required
Question 46
Question
The primary function of a surge arrestor in the top of a regulator is to:
Answer
-
allow the regulator to breath
-
reduce the opening speed of the regulator
-
limit the escape of gas to 1 cu. ft./hour
-
stop the regulator from operating if it is over pressurized
Question 47
Question
Propane containers located on the outside of a recreational vehicle shall be:
Answer
-
mounted securely to the roof of the vehicle
-
mounted on an “A” frame as close to the front of the vehicle as practicable
-
secured ahead of the front bumper
-
secured to the rear of the vehicle
Question 48
Question
A monitor regulator:
Answer
-
is a redundant regulator which backs up the operating regulator
-
controls gas flow to the top of the diaphragm
-
reduces pressure from pounds to ounces
-
remains locked off until it is required
Question 49
Question
What is the maximum outlet pressure for a first stage regulator on a residential propane system?
Answer
-
11.0” w.c.
-
11 psi
-
10.0 psi
-
15.0 psi
Question 50
Question
For appliances with the same input, the size of the orifice used for a propane appliance should be:
Answer
-
the same size as the orifice used for natural gas
-
larger than the orifice used for natural gas
-
smaller than the orifice used for natural gas
-
< 3% the size of the orifice used for natural gas
Question 51
Question
What does movement of 1/43 ft. dial indicate when completing a gas meter pressure dial test?
Answer
-
the service regulator is malfunctioning
-
the static pressure is excessive
-
the working pressure is low
-
the piping is not gas tight
Question 52
Question
What should be done if it is noticed that a regulator set in a loading dock area is not protected against physical damage?
Answer
-
advise the customer to provide protection as soon as possible
-
notify the local gas utility that protection is required
-
advise the customer to contact the local gas utility
-
report the situation to the Technical Standard and Safety Authority immediately
Question 53
Question
What is the maximum permitted filling density of a cylinder with liquid propane (relative density = 0.51) by liquid volume? (liquid temperature assumed to be 40°F ( 4.5°C)
Question 54
Question
What will happen if the adjusting screw of a regulator is turned counter-clockwise decreasing the spring pressure?
Answer
-
the downstream pressure will remain the same
-
the downstream pressure will decrease
-
the upstream pressure will increase
-
the upstream pressure will decrease
Question 55
Question
A regulator is sized for the load it is to serve by:
Answer
-
multiplying the appliance input by 1.5 and selecting a regulator in that input range
-
checking the appliance rating plate and selecting a regulator for that input range
-
determining the pipe size of the appliance manifold and selecting a regulator in that input range
-
multiplying the appliance input by 1.25 and selecting a regulator in that input range
Question 56
Question
Which of the following are used in an absorption refrigeration cycle?
Answer
-
ammonia and helium
-
ammonia and hydrogen
-
ammonia and propane
-
ammonia and butane
Question 57
Question
What are the main components of a gas-fired refrigerator?
Answer
-
generator, evaporator, radiator, absorber
-
generator, evaporator, capacitor, absorber
-
generator, evaporator, compressor, absorber
-
generator, evaporator, absorber, condenser
Question 58
Question
Is it permissible to use the propane side of a refrigerator in a recreation vehicle while the vehicle is in motion?
Answer
-
no
-
no, unless the vehicle is only being moved to a more level location
-
yes
-
yes, if the vehicle is being moved 1 mile or less
Question 59
Question
How can the location of a leak in a heat exchanger be determined?
Answer
-
by using a flue gas analyzer and visual examination
-
by using a carbon monoxide detector and visual examination
-
by using a smoke generator and visual examination
-
all of the available choices
Question 60
Question
Why does the recommended range of CO2 in a conventional furnace differ from the ultimate amount of CO2 of 11.9%?
Answer
-
to provide a safety margin
-
to provide a higher efficiency
-
to maintain a neutral pressure point at the door catch
-
to maintain a low stack temperature
Question 61
Question
Net stack temperature is the flue gas temperature:
Answer
-
downstream of the draft hood
-
upstream of the draft hood
-
plus the ambient temperature
-
minus the ambient temperature
Question 62
Question
A forced draft burner has a blower that produces sufficient pressure to overcome the resistance of the:
Question 63
Question
When the installation of an appliance constitutes a conversion from another form of energy to gas, the installer must:
Answer
-
advise the user in writing of the procedure to follow to discontinue the supply of the former form of energy
-
remove all aspects of the previous installation
-
remove the electrical supply wiring from the panel
-
advise the previous energy supplier of the change
Question 64
Question
When the required minimum clearance for a vent connector is 9” (228 mm) to combustible material with no protection, what is the acceptable method to reduce the clearance by 3” (76 mm)?
Answer
-
use 0.05” (12 mm) insulating millboard spaced out 0.05 (12 mm) with noncombustible spacers
-
use 0.25” (6 mm) insulating millboard spaced out 1” (25 mm)
-
use 22 gauge sheet metal attached to the hot side of the-combustible material
-
use 28 gauge sheet metal spaced out 1” (25 mm) from the combustible material
Question 65
Question
What will happen when the neutral pressure point for a conversion burner is improperly set?
Question 66
Question
Gross stack temperature is the flue gas temperature
Answer
-
downstream of the draft hood
-
upstream of the draft hood
-
plus the ambient temperature
-
minus the ambient temperature
Question 67
Question
When using a gas detector such as a Drager or Gas Tec type, the most important aspect regarding the sample tube is that the:
Answer
-
detector is within the manufacturer’s date code
-
sample tube is within the manufacturer’s date code
-
detector has been inspected and verified
-
the sample tube is CGA approved
Question 68
Question
What is the minimum service clearance in front of a boiler?
Answer
-
18” (450 mm)
-
24” (600 mm)
-
36” (900 mm)
-
48” (1200 mm)
Question 69
Question
The high limit setting on a forced warm air converted furnace shall not exceed:
Answer
-
150°F (66°C)
-
200°F (90°C)
-
250°F (120°C)
-
350°F (180°C)
Question 70
Question
Increasing the burners air supply will have the following effect on the percentage of CO2 in the flue gases and stack temperature:
Answer
-
the percentage of CO2 will increase and the stack temperature will increase
-
the percentage of CO2 will decrease and the stack temperature will increase
-
the percentage of CO2 will decrease and the stack temperature will decrease
-
the percentage of CO2 will increase and the stack temperature will decrease
Question 71
Question
What is the minimum clearance to combustibles from the top of the plenum of a converted forced warm air furnace?
Answer
-
1” (25 mm)
-
3” (75 mm)
-
6” (150 mm)
-
12” (300 mm)
Question 72
Question
When using a flue gas analyzer, which measures CO2 and you are in doubt as to the accuracy of the reading, how would you verify the accuracy of the instrument?
Answer
-
by comparing it to a second sample
-
by comparing it to a known sample
-
by checking it against a gas meter test dial
-
by checking it against the appliance manufacturers maximum input rating
Question 73
Question
How far above the burner port does the centre line of the flue outlet have to be to convert a revertible flue furnace with a natural draft burner?
Answer
-
at least 6” (150 mm)
-
less than 12” (300 mm)
-
at least 12” (300 mm)
-
at least 24” (600 mm)
Question 74
Question
What will be the result if too large a fire pot is used in a converted furnace or boiler?
Answer
-
pulsation will occur
-
there will be poor efficiency
-
the limit control will be ineffective
-
the high limit switch will open
Question 75
Question
What is the minimum clearance to combustibles material from the sides of a converted boiler?
Answer
-
3” (75 mm)
-
6” (150 mm)
-
12” (300 mm)
-
18” (450 mm)
Question 76
Question
What should be done if a relief valve is leaking?
Answer
-
remove the valve and clean off the calcium deposits
-
replace the valve seat and check for the cause of the activation
-
replace the relief valve and check for the cause of the activation
-
open a tap and relieve the tank pressure until the flow stops at the relief valve
Question 77
Question
What is the pressure relief valve setting for most residential type water heaters?
Answer
-
75 psig (517 kPa)
-
100 psig (690 kPa)
-
150 psig (1034 kPa)
-
200 psig (1380 kPa)
Question 78
Question
From the following list, which is the best location for a combination heating system consisting of a water heater and air handler?
Answer
-
in the insulated but unheated attached garage
-
the water heater in the basement and the air handler in the attic
-
together in a central location in the basement
-
the air handler supported on top of a rear flue water heater in a closet space
Question 79
Question
Which of the controls listed below controls the gas pressure to the main burner, the temperature of the water, and turns off the gas when the pilot goes out?
Question 80
Question
Combination systems are sized to deliver __________ of the calculated heat loss of the building.
Answer
-
90%
-
95% to 105%
-
120%
-
200%
Question 81
Question
The recommended water temperature setting from a mixing valve to the domestic water system in combination heating systems that employ oil-fired water heaters for heating potable water and for space heating is:
Question 82
Question
The components of a copper fin tube, instantaneous water heater are a/an:
Answer
-
anti-scald device and a pump control
-
pump, pump control, flow switch, temperature/pressure relief valve, and a limit control
-
E.C.O., temperature and pressure relief valve, anode, and a dip tube
-
temperature and pressure relief valve, anode, and a limit control
Question 83
Question
The temperature of the water returning from the heating loop in a combination system employing a water heater for domestic hot water and space heating must be:
Answer
-
higher than the outlet temperature from the water heater
-
no more than 5°C (9°F) below the outlet temperature from the water heater
-
lower than the minimum temperature required to activate the burner
-
at least the set temperature of the domestic hot water supply
Question 84
Question
Describe the leak testing required when replacing an existing gas water heater.
Answer
-
soap or detection instrument using an inert gas using table 8.25.2 to determine test pressure and duration
-
soap or detection instrument at the normal working pressure
-
soap or detection instrument at 2 times the normal working pressure
-
soap or detection instrument and a 10 minute dial test or leak test at normal working pressure
Question 85
Question
The flow rate of water passing through a heating coil of an air handler is controlled by the:
Answer
-
aquastat on the water heater
-
balancing valve on the heating loop
-
mixing valve on the heating loop
-
mixing valve on the domestic hot water system
Question 86
Question
What will cause the E.C.O. to open?
Question 87
Question
When can combination-heating systems employing a water heater be attached to baseboards or radiators that were previously used for boiler heating?
Question 88
Question
What type of water heater can be installed in a bathroom?
Answer
-
direct vent
-
power vent
-
fan assisted
-
revertible flue
Question 89
Question
What is the minimum required clearance from combustibles to the top, bottom, and sides of a horizontal furnace?
Question 90
Question
When is it permissible to store propane cylinders in the basement of a new home for future connection to a construction heater?
Question 91
Question
Which instrument is used to determine the speed of a direct drive fan motor?
Answer
-
A voltmeter
-
A manometer
-
An anemometer
-
A tachometer
Question 92
Question
Which control will shut the gas flow off in a high efficiency furnace if the venter motor fails?
Answer
-
high limit switch
-
roll out switch
-
air proving switch
-
ignition switch
Question 93
Question
In a repair garage, an appliance shall be installed so that a component capable of igniting a flammable vapour is located at least ______________ above the floor.
Answer
-
18 inches (450 mm)
-
2 feet (600 mm)
-
4.5 feet (1500 mm)
-
6 feet (2 m)
Question 94
Question
What is the minimum distance that the vent from a 75,000 Btuh Category III furnace may terminate from a door?
Answer
-
1 foot
-
3 feet
-
6 feet
-
10 feet
Question 95
Question
Before lighting a burner in a steam boiler, ensure that:
Answer
-
there is water in the boiler
-
the temperature controller is set properly
-
the main burner test firing valve is turned on
-
the safety valves are open
Question 96
Question
On seasonal start up, a pool heater should run:
Answer
-
intermittently
-
continuously for 24 hours
-
continuously until the thermostat is satisfied
-
one hour on and one hour off until the thermostat is satisfied
Question 97
Question
Automatic chlorinators must be installed:
Answer
-
upstream of the heater
-
downstream of the heater
-
upstream of the filter
-
downstream of the filter
Question 98
Question
If the thermostat heat anticipator is set to too low a setting:
Answer
-
the space temperature will be too high
-
the space temperature will be too low
-
the burner will run until the desired space temperature is achieved
-
the circulating pump will run continuously
Question 99
Question
Aquastats respond to changes in:
Answer
-
flue gas temperature
-
water temperature
-
stack temperature
-
air temperature
Question 100
Question
The external bypass valve is set by:
Answer
-
shutting off the pump
-
viewing the burner flame size
-
determining the appliance input
-
determining the temperature rise across the appliance
Question 101
Question
What safety control protects a steam boiler if the condensate pump fails to return water to the boiler?
Question 102
Question
Condensate in a boiler heating system is:
Answer
-
water heated for use in restaurant equipment
-
water in a water boiler return line
-
water from the relief valve in a boiler
-
water in a steam boiler return line
Question 103
Question
A room heater installed in either a sleeping area or public area shall be:
Question 104
Question
Single wall vent connectors:
Answer
-
may pass through floors, ceilings or roofs provided a metal thimble is used
-
may pass through floors, ceilings or roofs provided the required minimum distance from combustible material is maintained
-
may pass through floors, ceilings or roofs provided they are insulated
-
shall not pass through floors, ceilings or roofs
Question 105
Question
An appliance vent shall terminate from any building mechanical air inlet by at least:
Answer
-
1 foot (300 mm)
-
3 feet (900 mm)
-
6 feet (1800 mm)
-
10 feet (3 m)
Question 106
Question
What material must be used for the vent connector on an appliance without flue gas dilution air?
Answer
-
22 B & SG (0.64 mm) aluminum
-
24 GSG (0.60 mm) galvanized steel
-
26 GSG (0.47 mm) galvanized steel
-
28 GSG (0.38 mm) galvanized steel
Question 107
Question
Which of the following statements is correct?
Answer
-
a draft hood will eliminate back drafts coming down the chimney
-
a draft hood will prevent a negative pressure inside the building
-
a draft hood will prevent a down draft from entering the appliance
-
a draft hood will prevent flue gases from entering a building
Question 108
Question
The function of a fixed draft hood is to ensure:
Question 109
Question
When sizing either a vent or chimney which will vent more than one natural gas appliance, which of the following could be used in determining the size of the common vent?
Answer
-
the area of the common vent shall equal the total area of all the flue collars
-
the area of the common vent shall equal the area of the largest single flue collar
-
the area of the common vent shall equal the area of either the largest draft control device outlet or the largest flue outlet plus 50% of the sum of the outlet areas of the additional appliances
-
the area of the common vent shall equal the area of either the largest draft control device outlet or the largest flue outlet plus 75% of the sum of the outlet areas of the additional appliances
Question 110
Question
There is a new forced air furnace equipped with an induced draft fan beside a conventional water heater in a basement. The customer has decided to enclose the area to make a separate furnace room. The house is approximately 25 years old and has a door separating the basement from the upper levels.
- Furnace input = 100,000 Btuh (8.1.2 and footnote)
- AWH input = 25,000 Btuh
- Enclosure = 10’ x 20’ x 7’
- Structure dimensions = 20’ x 30’ x 7’ x 3 (levels)
What size opening will be required in the furnace room door to provide sufficient combustion air from inside the home?
Answer
-
0 square inches
-
9 square inches
-
18 square inches
-
125 square inches
Question 111
Question
There is a new forced air furnace equipped with an induced draft fan beside a conventional water heater in a basement. The customer has decided to enclose the area to make a separate furnace room. The house is approximately 25 years old and has a door separating the basement from the upper levels.
- Furnace input = 100,000 Btuh (8.1.2 and footnote)
- AWH input = 25,000 Btuh
- Enclosure = 10’ x 20’ x 7’
- Structure dimensions = 20’ x 30’ x 7’ x 3 (levels)
What size opening is required in the furnace room door to provide sufficient ventilation air for the furnace room?
Answer
-
0 square inches
-
8 square inches
-
18 square inches
-
125 square inches
Question 112
Question
Ventilation air openings for gas appliances should be located:
Answer
-
at the lowest possible point communicating with the outdoors
-
at the highest possible point communicating with the outdoors
-
on the same horizontal plane as the combustion air opening
-
at or above the level of the burner
Question 113
Question
A draft hood for an appliance shall be:
Answer
-
located in a different room than the appliance it serves
-
located in the same room as the appliance it serves
-
installed on an appliance with an induced draft
-
sized to the existing vent connection
Question 114
Question
“Spillage” of flue gases at the appliance draft diverter would indicate that:
Answer
-
an updraft condition is present in the venting system of the appliance
-
there is excessive draft at the appliance
-
the venting system of the appliance is restricted
-
the appliance is under fired
Question 115
Question
A boiler room contains the following natural draft appliances:
- two hot water boilers, each firing at 750,000 Btuh
- 1 water heater firing at 270,000 Btuh
- 1 water heater firing at 30,000 Btuh
What is the minimum required combustion air opening?
Answer
-
100 square inches
-
200 square inches
-
900 square inches
-
1800 square inches
Question 116
Question
What is the minimum size required for the air supply opening given the information listed below?
All appliances are equipped with draft diverters, the building is of recent construction with close fitting windows and doors, vapour barrier and drywall and the total input of all appliances is 310,000 Btuh.
Answer
-
36 square inches (23000 mm2)
-
43 square inches (28000 mm2)
-
47 square inches (30000 mm2)
-
50 square inches (32000 mm2)
Question 117
Question
Which of the following instruments is used to check the pressure drop across an indoor coil?
Answer
-
a velometer
-
an inclined manometer
-
an anemometer
-
a psychrometer
Question 118
Question
What is the purpose of an air-proving switch in an electronic air cleaner?
Answer
-
it ensures the fan motor is running
-
it ensures the fan is running
-
it ensures the draft is correct
-
it ensures there is no negative air
Question 119
Question
What happens when the humidistat for a power humidifier closes?
Answer
-
the humidifier solenoid valve opens
-
the humidifier motor starts to turn
-
the furnace fan starts, then the humidifier starts
-
the gas valve opens the humidifier starts
Question 120
Question
How are electronic air cleaners wired?
Question 121
Question
Why is it important to position an electronic air cleaner correctly?
Answer
-
to ensure as much of the air is bypassed as is possible
-
to remove as many odours as possible
-
to ensure there is as much restriction to air flow as possible
-
to ensure an even distribution of air across the face of the filter
Question 122
Question
Plate humidifiers operate:
Answer
-
all the time the fan is running
-
only when the fan is on low speed
-
only when the fan is on high speed
-
only when the humidistat calls
Question 123
Question
The primary voltage for duct mounted electronic air cleaners is:
Answer
-
20 – 30 volts
-
120 – 130 volts
-
220 – 240 volts
-
9,000 – 12,000 volts
Question 124
Question
What is the most common transformer required for a power humidifier?
Answer
-
120 – 24 volt
-
240 - 24 volt
-
240 – 120 volt
-
120 – 240 volt
Question 125
Question
Heat which when added to or removed from a substance causes a change of temperature is:
Answer
-
superheat
-
specific heat
-
latent heat
-
sensible heat
Question 126
Question
Which device can be used to determine the restrictions in a duct system?
Answer
-
hydrometer
-
potentiometer
-
barometer
-
manometer
Question 127
Question
If the belt on a blower is too tight, the motor:
Answer
-
voltage will decrease
-
voltage will increase
-
current will decrease
-
current will increase
Question 128
Question
If the fan compartment door of an appliance is left off, the motor:
Answer
-
voltage will decrease
-
voltage will increase
-
current will decrease
-
current will increase
Question 129
Question
Where is the lowest air pressure in a forced warm air heating system?
Answer
-
in all ductwork
-
upstream of the blower
-
downstream of the blower
-
at the supply registers
Question 130
Answer
-
heat transfer through solid objects
-
heat transfer through fluids
-
a wave form of heat transfer
-
a form of latent heat transfer
Question 131
Question
Increasing the size of a blower pulley:
Question 132
Answer
-
shuts the blower off on safety only
-
starts the blower when the plenum is up to temperature
-
starts and stops the blower
-
ensures the burner will not start if overheating occurs
Question 133
Question
What is the minimum diameter of a pressure gauge needed to perform a leak test on gas piping?
Answer
-
2 in.
-
2 – 3/4 in.
-
3 in
-
3 – 1/2 in.
Question 134
Question
Ammeter’s can read what?
Question 135
Question
What are the millivolts power output on a closed circuit test?
Answer
-
20 to 30 mV
-
10 to 15 mV
-
2 to 4 mV
-
10 mV or less
Question 136
Question
A pilot with a lazy yellow flame would indicate?
Answer
-
Orifice too small
-
Mid to high gas pressure
-
Target pilot orifice
-
Orifice size too large
Question 137
Question
For flame rectification one of the most important things should be?
Question 138
Question
What makes a flame capillary sensor tube prove pilot to main gas valve?
Answer
-
Trial for ignition
-
Glow coil
-
Pilot flame
-
Intermittent pilot
Question 139
Question
Can a new installation of a fin type pool heater less than 250 MBtu be installed downstairs in a house?
Answer
-
Yes, if gas piping can support gas input
-
No
-
Yes, if pool heater is direct vented
-
Yes, if poll heater is close to chimney
Question 140
Question
When converting an oil furnace to gas what type of atmospheric burner can be used?
Question 141
Question
If the flue gases are removed from the front of the appliance we could assume that it's a?
Answer
-
1 to 3 flue pass boiler
-
2 to 6 flue pass boiler
-
2 to 5 flue pass boiler
-
2 to 4 flue pass boiler
Question 142
Question
Can a gas log fireplace be installed in a sleeping quarter?
Answer
-
Yes, if proper air supply is added
-
Yes, if the venting is over sized
-
No, even if new venting is installed
-
Yes, only if its a bed sitting room
Question 143
Question
What is the minimum distance that a vent from an appliance with an input of 110 Mbtu/h can be from a non-mechanical air supply?
Question 144
Question
On a pressuretrol, the main burner starts on?
Answer
-
Pressure rise
-
Water level
-
Pressure differential
-
Steam system output
Question 145
Question
On a hydronic heater system what control responds to a load change?
Answer
-
Low water cut off
-
Expansion tank
-
Flow switch
-
Aquastat
Question 146
Question
When installing propane tanks under 1,000 USWG, what would be the minimum distance from a building?
Answer
-
25 ft.
-
30 ft.
-
15 ft.
-
10 ft.
Question 147
Question
If an appliance is less than 83% efficient and non-positive it would be considered a?
Answer
-
Category II
-
Category I
-
Category IV
-
Category III
Question 148
Question
For a steam boiler, what would be the most important safety control?
Question 149
Question
For a low-pressure steam boiler what would be the maximum steam pressure setting?
Answer
-
30 psig
-
25 psig
-
10 psig
-
15 psig
Question 150
Question
How would you measure relative humidity?
Answer
-
Wet bulb and atmospheric pressure
-
Dry bulb and latent heat of vapour
-
Moisture bulb and wet bulb
-
Wet bulb and dry bulb
Question 151
Question
What is nitrogen known as?
Answer
-
Toxins
-
Explosive gases
-
Inert gas
-
Neutralizers
Question 152
Question
Which heat is removed or added to cause a change in state without change in temperature?
Answer
-
Sensible heat
-
Radiant heat
-
Latent heat
-
Super heat
Question 153
Question
Except when permitted, what is the minimum clearance to combustibles from the top of a gas refrigerator?
Answer
-
2 in.
-
10 in.
-
36 in.
-
12 in
Question 154
Question
On a gas regulator, what controls the increase or decrease of gas flow to the appliance?
Answer
-
Restricting element
-
Vent hold
-
Loading element
-
Measuring element
Question 155
Question
When sizing capacitors in series, what would be the total capacitance (CT) using 12F and 15F capacitors?
Answer
-
5.66 CT
-
6.35 CT
-
6.97 CT
-
6.66 CT
Question 156
Question
What would be the Btu/h output of a 10 kW heater
Answer
-
38,210 Btu/h
-
36,220 Btu/h
-
33,150 Btu/h
-
34,120 Btu/h
Question 157
Question
Clocking a 5 cu ft. dial on a gas meter for 63 seconds, what would be the appliance input?
Answer
-
258 MBtu/h
-
286 MBtu/h
-
268 MBtu/h
-
284 MBtu/h
Question 158
Question
What does a gas pressure regulator control?
Answer
-
Inlet pressure
-
Gas flow
-
Downstream pressure
-
Locks out gas flow
Question 159
Question
A first stage or high-pressure regulator reduces tank pressure to...?
Answer
-
350 Psig to 10 Psig
-
375 Psig to 5 Psig
-
250 Psig to 10 Psig
-
375 Psig to 10 Psig
Question 160
Question
On a regulator, what senses outlet pressure?
Answer
-
Restricting element
-
Measuring element
-
Loading element
-
Spring element
Question 161
Question
Which gas meter would be used for a small or mid size commercial installation?
Answer
-
Rotary type
-
Tubing type
-
Bellows type
-
Orifice
Question 162
Question
A bellows gas meter is also known as a?
Answer
-
Down stream displacement meter
-
Up stream displacement meter
-
Pressure displacement meter
-
Positive displacement meter
Question 163
Question
A fan assist burner is?
Answer
-
Designed for better combustion
-
Designed for conversion boiler
-
Designed to overcome appliance friction
-
Designed to overcome burner resistance
Question 164
Question
A propane service regulator would normally deliver pressure at
Answer
-
Pound to 11 in. w.c.
-
Ounces to 7 in. w.c.
-
Ounces to 11 in. w.c.
-
Pound to 7 in. w.c.
Question 165
Question
What monitors water flow in a pool heater?
Answer
-
Aquastat
-
Low water cut off
-
Pressure switch
-
Flow switch
Question 166
Question
On a gas regulator, what is used to adjusts the outlet pressure?
Answer
-
Restricting element
-
Loading element
-
Limiting orifice
-
Measuring element
Question 167
Question
Venting spillage can be caused by?
Answer
-
Improper combustion air mixture
-
Excessive elbows in venting system
-
Cracked heat exchanger
-
Blocked condensate furnace drain
Question 168
Question
When vent spillage occurs and flue gases pass back through the combustion zone, what change occurs?
Answer
-
Flue gases are hotter and rise faster through chimney
-
Flue CO2 gases are more efficient
-
Flue CO2 gases changes to N2
-
Flue CO2 gases changes to CO
Question 169
Question
For a freestanding propane range in a large kitchen, the flexible connector may be how long?
Question 170
Question
An inverted sensor (measures water level) can be found operating what type of appliance?
Question 171
Question
What would be the input of a 0.60-gph-oil nozzle?
Answer
-
73 MBtu
-
70 MBtu
-
84 MBtu
-
50 MBtu
Question 172
Question
On a high efficiency furnace, what turns on the blower fan?
Answer
-
Klixon limit
-
Bi-metal switch
-
Relay timer
-
Temperature
Question 173
Question
A vent-limiting orifice is only allowed to approximately discharge how much gas in a 24-hour period?
Answer
-
1 cubic foot
-
10 cubic feet
-
20 cubic feet
-
24 cubic feet
Question 174
Question
What is the ultimate reading of CO2 (carbon dioxide) for natural gas?
Question 175
Question
What would be the approximate O2 (oxygen) reading?
Question 176
Question
What does a barometric damper control?
Answer
-
Excess Air
-
Pilot Air
-
Draft Air
-
Ventilation Air
Question 177
Question
A coil type boiler less than 400 MBtu would need a:
Answer
-
Spill switch and Low water cut off
-
Low water cut off and hi limit
-
Flow sensor and hi limit
-
Spill switch and hi limit
Question 178
Question
A portable infrared heater that cannot be interlocked shall be connected to a:
Answer
-
CO2 monitor alarm
-
CO monitor alarm
-
O2 monitor alarm
-
CO and O2 monitor alarm
Question 179
Question
On a decorative appliance with an H-shape burner, the carry over ports ensures:
Question 180
Question
The temperature of a high intensity infrared heater could reach up to:
Answer
-
1000°F
-
1800°F
-
1200°F
-
2025°F
Question 181
Question
Stack effect means?
Answer
-
Air flow though the appliance
-
Negative building pressure
-
Warm air will rise
-
External building envelope
Question 182
Question
What could be the problem if a domestic hot water tank dropped in temperature after five minutes of use?
Answer
-
Low gas input
-
Mixing valve
-
Broken dip tube
-
Gas valve
Question 183
Question
What is the minimum location from a property line that a pool heater can be installed?
Answer
-
24 in.
-
20 in.
-
18 in.
-
12 in.
Question 184
Question
Standard sizing for a circulating pump would be?
Answer
-
1 gpm per 2,000 Btu
-
3 gpm per 20,000 Btu
-
1 gpm per 1,000 Btu
-
1 gpm per 10,000 Btu
Question 185
Question
If you had a commercial air handler and needed to know the speed of the blower where the pulley on a five-horse power 3,450-rpm motor is 6-inch and the pulley on a two-inch-fifteen-foot drive shaft is 10-inch, what would be the rpm of the blower?
Answer
-
3450 rpm
-
2070 rpm
-
1725 rpm
-
863 rpm
Question 186
Question
What is the total diameter of a 4L-28 "V" drive belt?
Answer
-
280 in.
-
35 in.
-
28 in.
-
2.80 in.
Question 187
Question
What is the spark gap required for a spark ignitor?
Answer
-
1/4 to 3/8 in.
-
3/8 to 1/2 in.
-
1/16 to 3/16 in.
-
1/8 to 3/16 in
Question 188
Question
On a direct spark ignition control, what is the trial for ignition?
Answer
-
10 seconds
-
0.8 seconds
-
4 seconds
-
2 seconds
Question 189
Question
A pilotstat will de-energize after how many seconds?
Answer
-
0.8 seconds
-
10 seconds
-
90 seconds
-
4 seconds
Question 190
Question
What does a heat anticipator do?
Answer
-
Shuts the burner down if loss of gas supply
-
Determines the length of the burner "on" cycle
-
Acts as a back up safety limit
-
Shuts down burner on excess flow
Question 191
Question
Can NMD wire be installed to an outside gas lamp?
Question 192
Question
How many cubic feet of vapor will one pound of liquid propane (C3H8) expand to?
Answer
-
5.1 cu ft.
-
8.0 cu ft
-
7.5 cuft.
-
8.5 cu ft.
Question 193
Question
What does a spiral baffle do?
Answer
-
Remove flue gas
-
Speed up combustion
-
Slow flue gas
-
Raises flue temperature
Question 194
Question
When converting a furnace, how far above the burner must the flue collar be?
Answer
-
6 in.
-
8 in.
-
10 in.
-
12 in.
Question 195
Question
What would be the approximate time for purging a 1-inch NPS pipe at 100-feet?
Answer
-
50 seconds
-
1 minute
-
1 minute, 24 seconds
-
1 minute, 10 seconds
Question 196
Question
Natural gas is mostly made up of?
Answer
-
Methane and Butane
-
Methane and Ethane
-
Ethane and Butane
-
Butane and Propane
Question 197
Question
On a 14 /12 pitch roof, what would be the termination of a 5-inch B-Vent?
Question 198
Question
For a 20 horsepower steam boiler, what would be its maximum input in Btu?
Answer
-
200 Mbtu
-
530 Mbtu
-
680 Mbtu
-
700 Mbtu
Question 199
Question
On category IV appliances, can a single wall vent be used to vent flue gases?
Question 200
Question
At what temperature do flue gases condensate?