HVAC
AHU
- Damper
- adjust air volume flow rate by altering air passage cross-section with opposing blades rotating on horizontal pins.
- opening control by servo motor handled by automatic control syustem.
- Parallel blades
- deflection and shut-off purpose
- Opposing blades
- controlled synchronously
- Mixed Air Chamber
- 2-way
- outdoor ventilation mix with return air
- minimize energy consumption
- 3-way
- incorporates separate return air fan
- use opposing blades damper
- free cooling
- when outdoor isat or slightly below indoor design T
- activated by having outdoor air damper on open position to supply up to 100% outdoor air without operating air-conditioning equipment
- 2-way
- Air Filter
- Mechanical
- Bag Type
- MERV: 13-16
- Box Type
- high efficiency particulate air (HEPA)
- MERV: 17-20
- ultra low penetration air (ULPA)
- MERV: 17-20
- high efficiency particulate air (HEPA)
- Pleated Type
- MERV: ~6
- Bag Type
- Elastrostatic
- >95% on Arrestance (not efficient) scale
- washable
- MERV: 4
- Minimum Efficiency Reporting Value (MERV)
- Mechanical
- Air Conditioning Source
- Heating
- furnace
- boiler
- Cooling
- DX Coil
- Water Coil
- Heating
- Humidifier
- Supply Air Fan
- fan position
- Draw-through
- generate better uniform air flow across cooling/heating source
- carry over condensation from cooling source due to air dehumidification
- Blow-through
- Draw-through
- fan type
- centrifugual
- pulled along fan shaft and blown radially away from shaft in scroll casing
- forward curved (FC)
- backward curved (BC)
- Airfoil fan
- centrifugal fan with BC blades thickened twice
- highest efficiency
- Airfoil fan
- axial
- pulled along fan shaft and blown along in same direction
- propeller
- tubeaxial
- vaneaxial
- centrifugual
- fan position
- Air Distribution
- Air conveyance
- fittings
- ducts
- metal duct (rigid)
- least heat loss/gain
- least fan operating cost
- non-metal duct (flexible) - fibreglass
- insulation
- light weight
- low cost
- sound absorbing
- rectangular: fibreglass board
- round: fiberglass aluminum foil
- noise reduction
- vibration
- canvas (flexible) connection @ inlet & outlet opentings
- residual
- inner duct surface with acoustical board
- vibration
- return air
- return-air plenum space for small area
- vast space in drop ceiling
- low air velocity for noise reduction
- return-air plenum space for small area
- metal duct (rigid)
- Room distribution
- ceiling distribution
- ceiling/linear diffuser
- include volume control damper
- excellent for cooling & heating
- without undue draft or local discomfort
- cooling only
- ceiling/linear diffuser
- inside wall distribution
- register
- grille with volume control damper
- register
- perimeter distribution
- along exposed perimeter of space
- optimum comfort for winter heating
- grille
- fixed/adjustable blades directing flow only
- air outlet performance
- noise
- noise criteria (NC)
- increase NC, decrease size of outlet
- noise criteria (NC)
- outlet/face velocity
- 500 to 800 fpm
- throw
- distance b/w outlet and occupied zone
- drop
- vertical distance supply air has fallen at the end of throw
- terminal velocity
- 50fpm at the end of throw
- noise
- ceiling distribution
- Air conveyance
- Damper