Apuntes
Physical Layer Cabling: Twisted-Pair Notes
Contenido del apunte (1)
Página 1
Physical Layer
Cabling: Twisted Pair
Introduction
Examines the
twisted-pair media used to link computers together to form a local area
network (LAN). This is all a part of the Physical Layer of the OSI
model.
The main focus is on
unshielded twisted-pair (UTP) though an overview of shielded
twisted-pair (STP) is presented.
Chapter describes the six
subsystem of a structured cabling system.
Structured Cabling
The first
standard describing structured cabling system was TIA/EIA 568-A in
1995.
EIA is the
Electronic industries Alliance, a trade organization that lobbies for
the interests of manufactures of electronics-related equipment.
TIA stands for the
Telecommunications Industry Association, which is a trade organization
that represents the interests of the telecommunications industry.
Addendum 5 in 1999 was
the most important change to the standard because it defied the
transmission performance specifications for 4-pair 100-ohm category 5e
twisted-pair cabling.
They adopted the new
category 6 cable specifications in 2002, which is the recommended
cabling for use in today’s networks though CAT7 cabling may soon
become the recommended standard.
The EIA/TIA 568-A defines
the minimum requirements for the internal telecommunications wiring in
buildings and between structures in a campus network.
A campus network consists
of interconnected LANs within a limited geographic area such as a
college campus, military base, or group of commercial buildings.
In 2000 a new standard was
published called EIA/TIA 568-B with three parts:
EIA/TIA-568-B.1:
Commercial Cabling Standard, Master Document.
EIA/TIA-568-B.2:
Twisted-pair Media
EIA/TIA-568-B.3: Optical
Fiber Cabling Standard
With the EIA/TIA568-B
standard define the six subsystems of a structured cabling system:
Building
Entrance: The point where the external cabling and wireless services
interconnect with the internal building cabling in the equipment room.
Used for both public and private access. Also called the Entrance
Facilities (EF). Both public and private network cables enter the
building at this point, and typically each has separate facilities for
the different access providers.
Equipment Room (ER): A
room set aside for complex electronic equipment such as the network
servers and telephone equipment.
Telecommunications
Closet: The location of the cabling termination points that includes
the mechanical terminations and the distribution frames. The
connection of the horizontal cabling to the backbone wiring is made at
this point. This is also called the telecommunications room (TR) or
telecommunications enclose (TE).
Backbone Cabling: Cabling
that interconnects telecommunication closets, equipment rooms, and
cabling entrances in the same building and between buildings.
Horizontal Cabling:
Cabling that extends out from the telecommunications closet into the
LAN work area. Typically, the horizontal wiring is structured in a
star configuration running to each area telecommunications outlet
(TCO). This is the wall plate where the fiber or twisted-pair cable
terminates in the room. In some cases, the TCO terminates telephone,
fiber and video in addition to data into the same wall plate.
Work Area: The location
of the computers and printers, patch cables, jacks, computer adapter
cables, and fiber jumpers.
One room can
serve as the entrance facility, equipment room, and the
telecommunications closet.
Structuring
Main
Cross-Connect (MC): Usually connects two or more buildings and is
typically the central telecommunications connection point for a campus
or building. It is also called the main distribution frame (MDF) or
main equipment room. The MC connects to telco, an ISP, and so on.
Another term for MC is the campus distributor (CD).
Intermediate
Cross-Connect (IC): Also called the building distributor (BD), this is
the building’s connection point to the campus backbone. The IC links
the MC to the horizontal cross-connect (HC).
The Telecommunications
Cabling System Architecture
A cross-connect
is a space where you are going to take one or multiple cables and connect
them to one or more cables or equipment.
Typically connectors between
the MC and IC are single-mode and multi-mode fibers and possibly coax for
cable tv, although most installations are migrating to fiber.
Horizontal Cross-connect
(HC): The connection between the building distributors and the horizontal
cabling to the work area or workstation outlet: another term used for the
HC is the floor distributors (FD).
Workstation or Work Area
Outlets (WO): Also called the TO (telecommunications outlet). It’s used
to connect devices to the cable plant. The cable type typically used is
CAT3/5/5e/6/6A or various coaxial cables. Devices typically connected to
these outlets are PCs, printers, servers, phones, televisions, and
wireless access points.
The Campus Network
Hierarchical Topology
Horizontal
Cabling
Permanent network cabling within a building is
considered to be horizontal cabling, defined as the cabling that extends
out from the telecommunications closet into the LAN work area.
The Following components
are typically found in the telecommunications closet:
Backbone
Cabling interconnecting this closet with other closets
Switch or Hub
Patch Panels
Patch Cables
Cabling to the LAN
(horizontal cabling)
Wall Plate
Patch cable connecting the
computer to the wall plate
Unshielded
Twisted-Pair Cable
Category Cables
CAT6/5e/5
twisted-pair contains four twisted wire pairs for a total of eight
wires.
Twisted-pair
cables don’t connect to ground, the signals on the wires are set up
for a high (+) and low (-) signal line. Both signals are relative to a
virtual ground.
Balance Mode -- the balance of the two wire pairs helps
maintain the required level of performance in terms of crosstalk and
noise rejection.
Categories
Category 3
(CAT3)
Telephone
installations Class C
Up to 16 Mbps
Category 5 (CAT5)
Computer
Networks Class D
Up to 100 MHz / 100 Mbps
100-m length
Enhanced Category 5
(CAT5e)
Computer
Networks
100 MHz / 1000 Mbps
applications with improved noise performance in a full duplex mode.
Category 6 (CAT6)
Higher-speed
Computer
Up to 250 MHz networks
Class E / 1000 Mbps CAT6 supports 10 Gbps but at distances fewer than
100 meters.
Category 6a (CAT6a)
Increased
bandwidth
Up to 500 MHz networks
Class Ea / 10 Gbps
Category 7 (CAT7)
International
Organization for Standardization (ISO) standard, not an EIA/TIA
standard
Up to 600 MHz speed
computer networks Class F / 10 Gbps
Category 7a (CAT7a)
ISO standard,
not an EIA/TIA standard
Up to 1000 MHz speed
computer networks Class FA / 10 Gbps
CAT1 and CAT2 are not in
the EIA/TIA 568B standard, CAT3 is bing replaced with CAT5e or better
and CAT4 because it was removed for being outdated.
FastEthernet is used to
describe the 100 Mbps data rate for FastEthernet networks.
Network Congestion or
Bottlenecking is a slowdown on network data traffic movement.
Can be caused
by file size and limited bandwidth.
Full Duplex means that the
computer system can transmit and receive at the same time.
Terminating CAT6/5e/5 UTP
Cables
Wiring
Guidelines
Within the
EIA/TIA-568-B standard are the wiring guidelines T568A and T568B, they
specify the color of wire that connects to which pin on the connector,
called the color map.
There
is no difference between the two wiring guidelines, just different
manufacturer standards to be used, most use T568A.
Computer
Communication
Speeds of 10 Mbps / 100
Mbps use two of the twisted-pairs.
For communication to work
in a LAN, transmit and receive pairs must be properly aligned.
The transmit (TX) (+) and
(-) signals must connect to the receive (RX) (+) and (-).
In
a LAN, proper alignment is managed by a switch or hub.
When operating at 1 Gbps
and 10 Gbps speeds the signal names for a UTP cable are different and
all four of the wire pairs are used.
The
data is bidirectional, which means the same wire pairs are being used
for both transmitting and receiving data.
Straight-through
and Crossover Patch Cables
Straight-through
has all wires connected to the same corresponding pin on each end.
Crossover cable has the
transmit pair of device A connects to the receive pair of device B, and
transmit pair of device B connects to the receive pair of device A. If a
1 Gbps or 10 Gbps cable is set up all pairs are crossed.
Terminating a CAT6
Horizontal Link Cable
Inspect cable
for any damage.
At the work area outlet
end, add one foot extra and cut the wire. Coil the extra cable and
insert in the receptacle box. Cannot splice a CAT6 cable. At the
distribution end, route the cable and create a slack loop. Allow for 5
meters in the TC and 5 meters in the work area.
Place a bend limiting
strain relief boot on the cable. Strip 3 inches of cable jacket,
Remove the jacket from the
UTP cable and expose the four wire pairs.
Cut the plastic pull line
and the string. Place a lacing fixture on the cable and sort the wires
in either T568A or T568B.
Place the wires in the
slots of the lacing tool.
Align an RJ-45 (8P8C) jack
with the lacing fixture.
Insert the RJ-45 modular
jack into the AMP SL tool and then insert the RJ-45 jack into the AMP SL
tool.
Connect
the bend-limiting strain relief boot to the RJ-45 jack.
Assembling the
Straight-through CAT5e/5 Patch Cable
Inspect the
cable for damage.
Measure cable to length,
add about 6 inches and cut the wire. You can’t splice CAT5e/5
twisted-pair cable.
Strip about ¾ of an inch of
the cable jacket from the end of the cable using a cable stripper.
Sort the wire pairs so that
they fit into the connector and orient the wire in the proper order for
either T568A or T568B.
Clip the wires so that they
are even and insert the wires onto the RJ-45 modular plug.
Push the wires into the
connector until the ends of each wire can be seen through the clear end
of the connector.
Use a crimping tool to
crimp the wires onto the RJ-45 plug.
Repeat these steps for the
other end of the twisted-pair cable.
Cable Testing and
Certification
Link: Point from
one cable termination to another.
Full Channel: Consists of
all the link elements from the wall plate to the hub or switch.
Attenuation (Insertion
Loss): The amount of loss in the signal as it propagates down a wire or
fiber strand.
Near-end crosstalk (NEXT):
A measure of the level of crosstalk or signal coupling within the cable,
with a high NEXT (dB) value being desirable.
EIA/TIA 568B
Channel Specifications
Attenuation
(insertion loss): defines the amount of loss in signal strength as it
propagates down the wire. Test reports a margin, margin for attenuation
is defined as the difference between the measured value and the limit
for the test. If the margin shows a negative value the test failed. The
limit for CAT6 is 21.3dB, CAT6A is 20.9dB, CAT7 is 20.8 dB, and CAT7a is
20.3 dB. Bend Radius can also introduce attenuation loss.
NEXT:
When current travels in a wire, and electromagnetic field is created.
This can induce a voltage in adjacent wires resulting in crosstalk.
Crosstalk is what you occasionally hear on the telephone when you can
faintly hear another communication. NEXT is a measure of the level of
crosstalk, or signal coupling within the cable. More likely to happen
near the ends of the cable and is more problematic at higher data
speeds. A high NEXT (db) value is desirable.
Power Sum NEXT (PSNEXT):
This measures the total crosstalk of all cable pairs. This test ensures
that the cable can carry data traffic on all four pairs at the same time
with minimal interference. A higher value is desirable as it indicates
better cable performance.
Equal Level FEXT (ELFEXT):
Measures for the far end of the cable, and doesn’t depend on the length
of the cable. ELFEXT is obtained by subtracting the attenuation value
from the FEXT. A larger value is desirable.
PSELFEXT: Power sum ELFEXT
uses all four wire pairs to obtain a combined ELFEXT. A higher PSELFEXT
value indicates better performance.
ACR: Compares the signal
level from a transmitter at the far end to the crosstalk measured at the
near end. A larger ACR indicates greater data capacity and bandwidth.
PSACR: Power sum ACR uses
all four wire pairs to obtain the measure of the attenuation-crosstalk
ratio. Is the difference between PSNEXT and attenuation. Higher value
indicates better cable performance.
Return Loss: Provides a
measure of the ratio of power transmitted into a cable to the amount of
power returned or reflected. Reflection can be due to impedance changes
in the cable link which can contribute to cable loss. A low value is
desirable.
Propagation Delay: Measure
the amount of time it takes for a signal to go from end of the cable to
the other. Delays are affected by nominal velocity of propagation (NVP)
of the cable. NVP is some percentage of the velocity of light and is
dependent on the type cable being tested. Typical delay value is 5.7
nsec per meter. EIA/TIA allows for 548 nsec for 100 meter run.
Delay
Skew: Measures the difference in arrival time between the fastest and
slowest signal in a UTP wire pair. Data on the wire pair needs to arrive
at the other end at the same time. Different lengths of wires will cause
one to take longer than the other which can cause data and data packet
loss. Shortest length will typically have the least delay skew.
10 Gigabit
Ethernet over Copper
Overview
Ethernet over
copper is available for 10 Mbps (Ethernet), 100 Mbps (FastEthernet),
1000 Mbps (gigabit Ethernet), and 10 Gbps (ten gigabit Ethernet).
Three improvements required for higher
data bit over copper:
Improve the
cable so it can carry greater bandwidth
Improve the electronics
used to transmit and receive (recover) the data.
Utilize improvements in
both the cable and electronics to facilitate greater bandwidths and
distance.
IEEE 802.3an-2006
10GBASE-T is the standard developed to support running 10 Gbps data
over twisted-pair cabling. This requires the bandwidth to be increased
from 250MHz to 500MHz.
Alien Crosstalk
Alien Crosstalk
(AXT) is unwanted signal coupling from one permanent link to another.
This is an important issue at higher data rates, and the coupling of a
signal from one 4-pair cable to another 4-pair cable.
Alien Crosstalk is
considered to be the main electrical limiting parameter for 10G
Ethernet. It causes disturbances in the neighboring cable.
Cable manufactures are
starting to offer CAT6 and higher grades of twisted-pair cable with
foil over each of the four wire-pairs. The designation of this type is
F/UTP. Advantages are:
A shielded
cable offers better security because there is less chance that the
data will radiate outside the cable.
The foil shield helps
improve noise immunity from EMI, radio frequency interference (RFI),
and (most importantly) AXT.
Transmission over
twisted-pair cabling relies on the signals being “balanced” over the
wire pairs. The balance helps minimize unwanted leakage of signal.
TCL (Transverse Conversion
Loss) measurement is obtained by applying a common-mode signal to the
input and measuring the differential signal level on the output, also
sometimes called LCL (Longitudinal Conversion Loss).
TCTL (Transverse
Conversion Transfer Loss) is the loss from a balance signal at the
near-end to the unbalanced signal at the far end.
ELTCTL (Equal Level
Transverse Conversion Transfer Loss) is the difference between the TCTL
and the differential mode insertion loss of the pair being measured.
These tests have been
developed to help ensure compatibility with data transmission and
reception that requires the use of all four wire-pairs.
PSANEXT
(Power-Sum Alien Near-End Cross-Talk)
PSAACRF (Power-Sum Alien
Attenuation Cross-Talk Ratio Far-End)
Signal Transmission
The 10GBASE-T
system requires the use of all four wire pairs. It splits the 10 Gbps
of data into four 2.5 Gbps data channels. Requires the use of signal
conditioners and digital signal processing (DSP) circuits for both
transmission and reception. The data transmission for 10 gigabit uses a
multilevel encoding technique that reduces the required bandwidth to
transport the data.
10GBASE-T data
transmission also requires the use of DSP Compensation Techniques.
The DSP
circuitry provides many functions:
Signal
Conditioning
Echo Cancellation
In 10GBASE-T, the transmit
and receive signals are sharing the same wire pair. This is called full
duplex transmission and requires the use of a device called a hybrid
echo cancellation circuit which removes the transmitted signal from the
receive signal.
Cabling
systems that will support 10GBASE-T are CAT6 with the foil screen,
CAT6a, CAT7, and CAT7a.
Troubleshooting Cabling
Systems
Installation
If you obtain
bad Power-Sum or NEXT or FEXT, there might be a problem with the
installation.
A NEXT failure is most
likely due to a problem at the terminations. Most commonly the
installer has allowed too much untwisted cable at the termination point
(less than 3/8 inch). Inspect the terminations.
Cable Stretching
Avoid
stretching of the UTP cable because it changes the electrical
characteristics of the cable, increasing the attenuation and crosstalk.
Cable Failing to Meet
Manufacturer Specifications
Manufacturers
do experience problems with the cable failing to meet specifications
due to bad production run. Test failures with no apparent reason for
the failure could indicate that the problem is with the cable.