Water collection
sewer systems
- Combined sewer systems
- carries both foulwater and stormwater
- only one pipe is required and its capacity needs to be little more than that of a storm sewer system
- disadvantage is that large quantities of polluted water (a mixture of stormwater and foulwater) must be bypassed to watercourses during storm events to avoid overloading sewage treatment works
- separate systems
- higher initial capital costs
- foulwater is conveyed to the treatment works for purification before discharge to a watercourse, while the stormwater is discharged directly to a receiving water through the storm sewer system
- necessary to have at least one open vent
- The vent pipe ensures that the pressure within the domestic drainage system does not fall below atmospheric pressure and so risk water being siphoned from sanitary fixtures.
- In addition, the vent pipe assists in ventilating the public sewer and prevents foul air from the sewer entering the internal building foul drainage system.
- Combined sewer systems
Design considerations
- normally flow partially full and therefore rely on pipe gradient to convey the wastewater along the pipe
- sewers must be adequate in size and gradient, so that they will carry the maximum (design) flow without being surcharged
- minimum cleansing velocities
- to prevent the deposition of solids in the sewer system at low flows
- If adequate gradient is not available due to ground topography, the wastewater is normally collected by gravitational flow to some convenient low-point, from where it is pumped
- material must be selected so as to be capable of withstanding external loading
- selection of pipe material
- wastewater must not be aggressive to the wall of the sewer
- manhole covers every 100- 150m
- normally flow partially full and therefore rely on pipe gradient to convey the wastewater along the pipe
waste water flows
- dry weather flow (DWF) is approximately equal to the flow of drinking water supplied to an area
- 225 litres/head/day
- designed to cater for 3 DWF
- combined sewer systems
- much lower potential for polluting watercourses
- foul water very diluted
- 6 DWF
- to ensure that, under storm conditions, the most polluting component of the wastewater (frequently termed the ‘first foul flush’) is transported to a treatment works
- The remaining stormwater flow (which could be large as 40 DWF) is generally ‘offloaded’ from the sewer system by means of storm overflows to adjacent watercourses
- Under storm conditions, about 3 DWF of the incoming 6 DWF is temporarily stored on site in balancing tanks until the storm abates
- dry weather flow (DWF) is approximately equal to the flow of drinking water supplied to an area
storm sewer design
- influencing factors
- rainfall
- catchment
- sewer network
- starting size of pipe
- 150 mm in diameter
- flow velocities
- not too high to be abbrasive
- max 3.5 m/s
- not too low so solids are deposited
- 0.75m/s
- 3DWF
- 675 litres/head/day
- not too high to be abbrasive
- influencing factors
Pumping stations
- dry well suction pump
- installed in a dry chamber or well, adjacent to the wet-well (also referred to as the pump sump)
- wet-well serves to equalise the incoming flow, which is always variable
- advantage
- configuration is the relatively greater facility for inspection and maintenance
- submerisable pump
- Both the pump and the motor are housed in a waterproof casing
- submerged in the liquid being pumped
- disadvantage
- maintenance of the pump-motor assembly is a more disagreeable task
- Both the pump and the motor are housed in a waterproof casing
- dry well suction pump
storm overflows
- frequently result in watercourses being polluted by untreated sewage
- storm flow characteristics
- should not come into operation until the prescribed flow is being passed to treatment
- flow to treatment should not increase significantly as the amount of overflowed storm sewage increases
- maximum amount of polluting matter should be retained in the forward flow to treatment
- chamber should be so designed as to minimise turbulence and risk of blockage
- hould be self-cleansing and require the minimum of maintenance