Unit 203 Revision: Installation Technology Question Bank No.1

Descrição

C&G 2365 Level 2 Unit 203 Revision OB
Oliver Balay
Quiz por Oliver Balay, atualizado more than 1 year ago
Oliver Balay
Criado por Oliver Balay quase 9 anos atrás
29143
12

Resumo de Recurso

Questão 1

Questão
A BS3036 protective device is a
Responda
  • Rewireable fuse
  • Cartridge fuse
  • Type B MCB
  • Type C MCB

Questão 2

Questão
A cable has resistance of 0.12 ohms and a current of 30A. The volt drop due to resistance is
Responda
  • 10.6V
  • 3.6V
  • 2.6V
  • 7.6V

Questão 3

Questão
A circuit supplying kitchen appliances would be identified as
Responda
  • Heating
  • Cooker
  • Lighting
  • Power

Questão 4

Questão
A circuit to supply hot water would be identified as
Responda
  • Floor warming installations
  • Heating
  • Power
  • Motor

Questão 5

Questão
A common method of providing protection by fault protection
Responda
  • ADS (Automatic disconnection of supply)
  • Enclosures
  • Placing out of reach
  • Insulation

Questão 6

Questão
A method of protection against electric shock is provided in a cable by
Responda
  • RCDs
  • Barriers
  • Automatic Disconnection of Supply (ADS)
  • Insulation

Questão 7

Questão
A work plan for new installations provides:
Responda
  • Cost of materials
  • Estimates of timescale
  • Safety information
  • Instructions for all workers

Questão 8

Questão
A requirement for safety that all installations should have is
Responda
  • Overcurrent protection
  • Energy meter
  • Fire alarm
  • Indication of supply failure

Questão 9

Questão
A short circuit occurs
Responda
  • Between two conductors on the same phase
  • Between two conductors at different potential
  • Between two conductors at the same potential
  • In a circuit that is electrically sound

Questão 10

Questão
A single pole switch breaks
Responda
  • The line and neutral conductors
  • The neutral conductor
  • The circuit protective conductor
  • The line conductor

Questão 11

Questão
A typical system application for fibre optic cable is:
Responda
  • Fire alarms
  • Data communications
  • Emergency management
  • Environmental control

Questão 12

Questão
A voltage of 400kV represents the following voltage
Responda
  • 0.4V
  • 40000V
  • 0.04V
  • 400000V

Questão 13

Questão
Aluminium may be used as a conductor in preference to copper as it is
Responda
  • Less likely to corrode
  • Is lighter
  • Is easier to terminate
  • Is a better conductor

Questão 14

Questão
Aluminium spiral fixings are used to fix items on
Responda
  • Concrete
  • Brick
  • Roof tiles
  • Plaster board

Questão 15

Questão
An Earthing system that uses a separate conductor as a return path for any fault current is called
Responda
  • TN-C-S
  • TT
  • TN-S
  • IT

Questão 16

Questão
An example of overload is
Responda
  • A 13 amp socket outlet with a 100W lamp connected
  • A 13amp socket outlet with a 2kW fire connected to it
  • A lighting circuit with a 100W lamp connected
  • A lighting circuit with a 2 kW heater connected

Questão 17

Questão
An RCD is a device used to protect circuits against
Responda
  • Overload and Earth faults
  • Earth faults only
  • Overload and Short Circuits
  • Short circuit only

Questão 18

Questão
Automatic disconnection of supply and special locations are found in
Responda
  • BS 7671
  • Electricity at Work Regulations
  • Jane Austin Novel
  • Health and Safety Policy

Questão 19

Questão
Best location for a solar panel
Responda
  • On the roof of a building facing north
  • On the side of a chimney
  • On the shaded part of the roof
  • On the roof of a building facing south

Questão 20

Responda
  • Cannot be tampered with
  • Are accurate at determining overload current
  • Will not cause damage in the event of severe short circuit
  • Have a re-wireable element

Questão 21

Questão
Circuit breakers are frequently installed in preference to fuses because
Responda
  • They are adjustable
  • They do not need replacing after operation
  • They are less sensitive to some types of fault
  • They are cheaper than fuses

Questão 22

Questão
Circuit breakers use two forms of operation
Responda
  • Thermal and magnetic
  • Thermal and bi- metallic strip
  • Fuse element and magnetic
  • Thermal and fuse element

Questão 23

Questão
Define the term for a Circuit Protective Conductor (CPC)
Responda
  • A cable that links all extraneous conductive parts backs to the MET
  • It is the cable that connects from the MET to the star point of the sub station
  • It relates to the types of dangerous gases that are released into the atmosphere
  • A cable that links all exposed conductive parts back to the MET

Questão 24

Questão
Determine the size of conduit required for a run of 2.7m, if you are installing 3 x 1.5mm² and 6 x 6mm² conductors (all stranded).
Responda
  • 16mm
  • 20mm
  • 25mm
  • 32mm

Questão 25

Questão
Determine the size of conduit required for a run of 2.9m, if you are installing 9 x 2.5mm² and 3 x 6mm² conductors (all stranded).
Responda
  • 20mm
  • 16mm
  • 32mm
  • 25mm

Questão 26

Questão
Equipment identified in BS 7671 by an EN number must comply with the relevant requirements of:
Responda
  • Extra neutral provision
  • European standards
  • Economic standards
  • English standards

Questão 27

Questão
ES lamp holders, the outer casing must be connected to
Responda
  • Neutral conductor
  • Line conductor
  • Earth conductor
  • All conductors

Questão 28

Questão
Excess current, flowing in a circuit which is electrically sound, is defined as
Responda
  • Short-circuit current
  • Earth fault current
  • Open-circuit current
  • Overload current

Questão 29

Questão
From BS 7671 the disconnection time for circuits supplying equipment and circuits up to 32A is :
Responda
  • 0.2s
  • 0.04s
  • 0.4s
  • 5s

Questão 30

Questão
What does Ze represent from the following formula Zs = Ze + (R1 + R2)?
Responda
  • Internal Earth Fault Loop Impedance
  • Resistance of the circuit protective conductor
  • External Earth Fault Loop Impedance
  • Resistance of the line conductor

Questão 31

Questão
What does R1 represent from the following formula Zs = Ze + (R1 + R2)?
Responda
  • Design Current
  • Resistance of the circuit protective conductor
  • Resistance of the line conductor
  • External Earth Fault Loop Impedance

Questão 32

Questão
From the On-site-Guide the maximum external earth loop impedance for a TN-C-S system is?
Responda
  • 0.08 ohms
  • 0.8 ohms
  • 0.85 ohms
  • 0.35 ohms

Questão 33

Questão
From the On-site-Guide the maximum external earth loop impedance for a TN-S system is?
Responda
  • 0.8 ohms
  • 0.75 ohms
  • 0.35 ohms
  • 0.08 ohms

Questão 34

Questão
Holes between joists must be of a minimum distance from top or bottom fixing surface of
Responda
  • 10mm
  • 20mm
  • 50mm
  • 60mm

Questão 35

Questão
Identify the distribution voltage for a large story building with a private transformer
Responda
  • 11kv
  • 400v
  • 110v
  • 12v

Questão 36

Questão
IET Wiring regulations give directives on electrical installations in hazardous environments, however the statutory governing these situations are covered in the:
Responda
  • British Standards
  • Electricity at Work Regulations 1989
  • Approved Codes of Practice
  • Health & Safety at Work Act 1974

Questão 37

Questão
IET Wiring regulations apply particularly to:
Responda
  • Mining industry
  • All branches of industry
  • Electrical manufacturing industry
  • Electrical contracting industry

Questão 38

Questão
IET Wiring regulations recommend inspection of temporary construction site installation every:
Responda
  • 1 month
  • 3 months
  • 12 months
  • 24 months

Questão 39

Questão
If a 20mm steel conduit was to be installed horizontally what would be the maximum spacing of supports
Responda
  • 1.00m
  • 1.75m
  • 2.25m
  • 0.75m

Questão 40

Questão
If a 30A fuse has a tripping characteristic of 5 x In, what would be the instantaneous tripping current?
Responda
  • 30A
  • 600A
  • 150A
  • 60A

Semelhante

WJEC Level 2 Latin Language Vocabulary (A)
Gian Hernandez
WJEC Level 2 Latin Language Vocabulary (T)
Gian Hernandez
Unit 203 Mock Installation Technology Questions
Oliver Balay
Unit 203 Revision Question Bank No.2
Oliver Balay
WJEC Level 2 Latin Language Vocabulary (E&F)
Gian Hernandez
Unit 203 Mock Installation Technology Questions
Jamie Parslow-Williams
WJEC Level 2 Latin Language Vocabulary (S)
Gian Hernandez
WJEC Level 2 Latin Language Vocabulary (M)
Gian Hernandez
WJEC Level 2 Latin Language Vocabulary (N)
Gian Hernandez
WJEC Level 2 Latin Language Vocabulary (I)
Gian Hernandez
Unit 203 Revision Question Bank No.2
carl tovey