  1. 1How many egresses (exits) gates are required for outdoor enclosures containing medical gas supply systems?
    1. A1
    2. B2
    3. C3
    4. DNFPA 99 does not state a requirement
  2. 2A positive pressure supply system has duplex line regulators piped in parallel. Which of these is NOT a requirement for the regulators?
    1. AConstructed of any materials deemed suitable by the manufacturer for the service.
    2. BEach regulator sized for 110 percent of peak calculated demand
    3. CIsolation or check valves on the patient side of the regulators
    4. DIsolation valves on the source side of each regulator
  3. 3What is the standard vacuum pressure for WAGD?
    1. A50-55 PSI
    2. B345-380 kPa
    3. C380 mm to 760 mm
    4. DIt varies with the type of system
  4. 4A valve installed in each med gas and vacuum system shall be tested to verify which of the following?
    1. ADate of installation
    2. BFlow and pressure drops
    3. CPressure range
    4. DProper operation and rooms or areas of control
  5. 5Brazing procedures and brazer performance for the installation of med gas and vacuum piping shall be qualified in accordance with which ?
    1. AASME section IX
    2. BASSE standard 6010
    3. CASTM B828
    4. DAWS B313
  6. 6A new bulk system is to be installed at a local hospital; therefore, new wiring from the local panel on the bulk must be run underground to the entry point of the facility. At a minimum, how many sets of wires for each signal are allowable between the initiating device at the bulk and junction box located in the facility?
    1. A1 or 2
    2. B1 or 3
    3. C2 or 3
    4. D2 or 4
  7. 7Which are may be acceptable to communicate with indoor central supply sources of oxygen, nitrous oxide, or mixtures of these gasses?
    1. AAn in-building emergency reserve location
    2. BAnesthetizing location
    3. CAreas of open flame
    4. DKitchen
  8. 8Medical Gas Systems shall be deemed breached at the point of pipeline intrusion ___ or by system component removal, or addition.
    1. AClosing of Valve
    2. BCylinder change out
    3. CPhysical separation
    4. DTesting
  9. 9Who shall witness both the installer performed standing pressure test and standing vacuum test?
    1. AInstallation contractor superintendent
    2. BMedical gas verifier
    3. CThe authority having jurisdiction or its designee
    4. DA witness is not required
  10. 10A medical air compressor intake piping shall be located a minimum of how many feet from any vent?
    1. A10
    2. B12
    3. C15
    4. D25

Informações

Descrição
Quiz sobre Med Gas Pre Test, criado por brandon_c28 em 16-01-2014.
Idioma
English
Visualizações
15.503
Etiquetas
hard
Avaliação
4,5 de 5 · 4 avaliações
Avalie este quiz
Avalie este quiz

Fale Conosco

Sobre o que é sua mensagem?

O que você acha do novo visual?

Você gostou?