  1. Design Life Cycle

    • Detailed Design
      • Storage Capacity
      • Controls
      • Pumps
      • Tank Lid
      • Materials used
      • Fuel tank storage and transportation
    • Construction
      • Materials
        • Tanks
        • Fuel pumps
      • Manufactoring
        • Workers
      • Function
        • Design Lifecylce
        • Usability of systems
    • Commissioning
      • Testing
      • Transportation of Storage Tanks
        • Via road tank or pipleines
      • Maintenance
    • Operating
      • Controls
        • Level Gauge
        • Monitoring systems
      • Operator Skill/Requirements
      • Function
    • Maintaining
      • Parts/Repair
      • Service Requirements
    • Decomissioning
      • Tanks
        • Only for qualified and competent technicians
          • tank must be fully drained, degassed and certified
  2. What Happened

    • 19.00, Tank 912 started receiving unleaded motor fuel; pumping at about 550 m3/hour (***)
    • 3:00, Tank fuel levels recorded unchanged reading, yet still continued to be fuelled
    • 05.20 Tank 912 would have been completely full. It now began to overflow (***)
    • 05.38 vapour from the escaping fuel is first visible in CCTV footage
    • 05.46 the vapour cloud had thickened to a depth of about 2 m and was flowing out of storage site onto all directions
    • At 06.01 the first explosion occurred, followed by further explosions and a large fire that engulfed over 20 large storage tanks.
    • The fire burned for several days, destroying most of the site, 2,000 homes were evacuated and 92 neighboring firms were affected
  3. Why it happened

    • Failures
      • People
        • Individual Factors
          • Designers and suppliers of independent level switch were poorly trained
          • The site operator did not exercise sufficient oversight of the ordering, installation and testing procedure
      • Workplaces
        • Workplace Factors
          • There was only one visual display screen for all the tanks which meant that the status of only one tank could be fully viewed at a time
          • lack of engineering expertise on site
        • Equipment Design
          • Automatic Level Gauge (ALG) did not function
          • Independent level switch was inoperative
            • Critical Padlock not fitted
          • On the tank screen mimic a red ‘stop’ emergency shutdown button was showed.
            • this was not working and had never been fitted into the system.
        • Work Environment
          • The ATG system hadn’t the set the alarm in the event of inconsistencies between tank level measurements and filling data
          • The lack of a maintenance regime
      • Management
        • Organisational/System Factors
          • None of the staff at the site was aware of the need for the padlock to be replaced
          • failure to implement management of change processes
        • Job Design
          • Poor shift working times meant workers were exhausted
          • poor communications at shift handover
        • Information transfer
          • Tank storage supervisors did not have access to monitoring screens - Lack of control of incoming fuel
          • No written evidence on which the tanks had to be filled
  4. System Parts

    • Tank
      • Vents on Tank roof
      • Automatic Level gauge
        • measured the rising level of fuel and displayed this on a screen in the control room
      • Access Hatch
      • vertical, cylindrical, non-refrigerated, above-ground
      • side walls greater than 5 m in height
      • Tankers operating from Buncefield were of 44 or 18 tonnes capacity
    • Staff
      • Tasks
        • Operators monitored the arrival of the various grades of fuel and separated them out into dedicated tanks by fuel type
      • Training
    • Oil Pumps
      • Independent High-level switch
        • Alarm Circuit
        • Check Lever
        • Critical Padlock
    • Storage and transfer depot
      • e three pipelines all transported fuel products in discrete batches, separated by an interface or buffer of mixed product
      • interface of mixed fuel was diverted to special small tanks to be reinjected into the main large storage tanks
      • separated products left the depot either by road tanker or, in the case of the majority of aviation fuel, via two dedicated pipelines

Information