- 1What else does stage 3 envelope flow model require/do? It uses the explicit method. - weather conditions - ventilation - openings- internal and external temperatures
- wind speed
- determine required ventilation rates
- calculate areas of openings to give required ventilation rates using envelope flow model - 2In stage 4 off-design calculations, for given openings, it determines flows using implicit method. What needs to be determined?• Fix opening sizes
• Choose off-design weather conditions
– Internal and external temperatures
– Wind speed
• Determine ventilation rates using envelope flow model
• Iteration of flow model required for solution - 3What are the 3 design conditions?1. Buoyancy only
2. Wind only
3. Buoyancy and wind combined - 4Buoyancy flow: - What does it use/include?- Hydrostatic pressure acting across surface.
- Openings allow air to flow into and out of the space
- Change in neutral height with opening sizes
- Identical openings NPL mid- point
- Different opening sizes shifts NPL vertically - 5Buoyancy flow: What is the pressure acting on the external surface (equal to the hydrostatic equation):

- 6Buoyancy flow: If is the internal temperature is uniform (hydrostatic equation acting on interl surfaces):

- 7Buoyancy flow: What is the pressure difference acting on the ith of j openings at height z, is:

- 8Wind driven flow: - Pressure? - Windside, leeward? - Roof?- Pressure distribution across surface of building
- Windward side: +ve
Leeward side: –ve
- Roof may produce +ve and –ve pressure distributions - 9Wind driven flow: Uniform density pressure on surface is sum of hydrostatic equation is? What is the internal pressure? Density is assumed as?

- 10Wind driven flow: What is Cp equal to? What is delta p equal to?

- 11Combined flow: What is the pressure difference acting across ith of j openings at height z? Or?

- 12Flow equation: Air flow through ith of j openings??

- 13What is the continuity equation Why is it needed? What does it state?This equation is fundamentally important to the prediction of a ventilation rate.
It states that the volume of air that enters a building must equal that leaving the building.
- 14What equations must openings have?

- 15See notes for example...
- 16Envelope flow models: For building with more than 3 opennings what must be used? What are the difference between the models?Method 2 is more accurate than method 1.

- 17See notes for explicit example...
- 18See example for explicit buoyancy method...
- 19See notes for example of explicit method for wind....
- 20See notes for combined explicit method....
- 21Implicit method: - Flow? - Neutral height? - Can envelope model be used? - Flow rate?

- 22Example of implicit method?- The Implicit method must be used to predict airflow through adventitious openings because airflow rates cannot be specified in advance.
- Areas can be estimated and so the airflow forgiven weather conditions is estimated. - 23Adventitious air leakage: - What is it? - How does it occur? - Airflow through small openings can e shown through what equation?Cracks and small openings, typically less than 10mm and usually much less.