  1. 1Gypsum board plenums shall be limited to return air systems where air temps do not exceed ________ degrees F.125
    (Duct Systems)
  2. 2Smoke detectors are not required to be installed in a return air system with a maximum design capacity of ___________ cfm.2,000
    (Duct Systems)
  3. 3Round metallic ducts shall be fastened by no less than ________ sheet metal screws or rivets _________ spaced.3
    equally
    (Duct Systems)
  4. 4Flexible air connectors (not flex ducts) shall be limited in length to ______ feet.14
    (Duct Systems)
  5. 5Air to be conveyed through flex ducts and flex connectors shall be less than ______ degrees F.250
    (Duct Systems)
  6. 6Underground duct slope must be at least __________ inch per foot.1/8
    (Duct Systems)
  7. 7Materials exposed within plenums shall be listed and labeled as having maximum flame spread index of ________.25
    (Duct Systems)
  8. 8Unless provided with an approved protective coating, metallic underground ducts shall be completely encased in a minimum of _____ inches of concrete.2
    (Duct Systems)
  9. 9Floor registers shall resist, without structural failure, a minimum _______ pound concentrated load.200
    (Duct Systems)
  10. 10Ducts that operate at temperatures exceeding _______ degrees F shall have sufficient thermal insulation to limit the exposed surface temperature.120
    (Duct Systems)
  11. 11Factory insulated flex ducts shall be printed or identified at maximum intervals of _______ inches.36
    (Duct Systems)
  12. 12Smoke detectors are not required in a return air system where all areas of the building served are _____________.protected by area smoke detectors connected to a fire alarm system
    (Duct Systems)
  13. 13The maximum permitted length of flexible air duct is _______.unlimited
    (Duct Systems)
  14. 14Where return air risers serve 2 or more stories, smoke detectors shall be installed at each story in return air systems with a design capacity greater than_______ CFM.15000
    (Duct Systems)
  15. 15Access points to permit inspection and maintenance of fire and smoke dampers shall be permanently identified by a label having letters not less than ________inch..5
    (Duct Systems)
  16. 16For duct wrap, the installed thickness shall be assumed to be ______ percent of nominal thickness75
    (Duct Systems)
  17. 17Joints for round and oval metal ducts shall be lapped not less than ____ inch.1
    (Duct Systems)
  18. 18Clothes dryer exhaust ducts shall be ______ inches in diameter.4
    (Duct Systems)
  19. 19Where multiple air handing systems share the same supply or return ducts with a combined capacity above _________ CFM, the return should be equipped with smoke detectors.2000
    (Duct Systems)
  20. 20Ventilation intake openings are permitted not less than _______ feet from a lot lines.10
    (Ventilation)
  21. 21When is a room required to be ventilated?When the room is occupied.
    (Ventilation)
  22. 22Outdoor air intake openings shall be permitted to be located less than 10 feet horizontally from a street , alley, parking lot or loading dock, provided the openings are located not less than ____________ feet vertically above such locations.25
    (Ventilation)
  23. 23Ventilation intake openings are permitted not less than ________ feet from buildings on the same lot.10
    (Ventilation)
  24. 24Ventilation intake openings are permitted not less than ________ feet horizontally from any hazardous or noxious contaminant source.10
    (Ventilation)
  25. 25What is the exhaust airflow rate for an embalming room?2 CFM per square foot.
    (Ventilation)
  26. 26Continuous ventilation shall be provided at a rate of not less than ______________.1 CFM/SF of floor area in the room
    (Ventilation)
  27. 27Supply air to a swimming pool and associated deck areas shall not be recirculated unless the air is dehumidified in order to maintain a maximum relative humidity of __________ percent.60
    (Ventilation)
  28. 28In addition to the general ventilation requirements, each manicure station in a nail salon shall be provided with a source capture system capable of exhausting a minimum of ________ CFM per station.50
    (Ventilation)
  29. 29Where exterior openings are utilized under the natural ventilation provisions for obtaining the required ventilation air, the minimum openable ventilating area to the outdoors shall be ___________ percent of the floor area being ventilated.4
    (Ventilation)
  30. 30Ventilation air shall not be recircuilated from one dwelling to another or to ___________ occupancies.dissimilar
    (Ventilation)
  31. 31The operating mechanism for openings providing natural ventilation shall be controllable by _________________.building occupants
    (Ventilation)
  32. 32In other than residential occupancies, the maximum opening size in a screen protecting an air intake opening in an exterior wall shall be _____________ inch(es) measured in any direction.1
    (Ventilation)
  33. 33Corridors are permitted to be used to convey air when they are located within tenant spaces of __________ square feet, or less in area.1000
    (Ventilation)
  34. 34When exhaust fans , clothes dryers, and kitchen ventilation systems interfere with the operation of appliances, ____________ shall be provided.make up air
  35. 35A vent connector shall be installed without any dips or sags and shall slope ______ toward the vent or chimney at least ________ inches per footupward
    .25
    (Chimneys and Vents)
  36. 36Chimney vents shall terminate not less than _______ feet above any forced air inlet located within ________ feet.3
    10
    (Chimneys and Vents)
  37. 37The termination of mechanical draft systems. when located adjacent to walkways, shall be not less than _______ feet above the level of walkway.7
    (Chimneys and Vents)
  38. 38In general, masonry chimney flues shall be provided with a cleanout opening having a minimum height of __________ inches.6
    (Chimneys and Vents)
  39. 39A cleanout for a chimney flue serving a masonry chimney is not required when the flue is provided with access through ________ .the fireplace opening
    (Chimneys and Vents)
  40. 40The termination of a vent with a power exhauster shall be located a minimum of _______ feet from adjacent buildings.10
    (Chimneys and Vents)
  41. 41Residential flue linings are permitted to be of any approved materials that will resist, without cracking, softening or corrosion, flue gases and condensate up to a maximum temperature of _______ degrees F.1800
    (Chimneys and Vents)
  42. 42Where vents pass through insulated assemblies, a ____________ shall be installed to provide the required clearance between the vent and the insulation material.26 GA sheet metal shield
    (Chimneys and Vents)
  43. 43Appliances with integral vents that use forced draft venting systems shall be located so that a minimum clearance of _______ inches is maintained between vent terminals and from openings into the building.12
    (Chimneys and Vents)
  44. 44For mechanical draft systems, horizontal vent terminations shall be located a minimum of ______ feet horizontally from any door or window.4
    (Chimneys and Vents)
  45. 45Manual chimney dampers shall not be installed in connectors except in _____________________________.chimney connectors serving solid fuel burning appliances
    (Chimneys and Vents)
  46. 46For mechanical draft systems, horizontal vent terminations shall be a minimum of ________ inches above finished grade12
    (Chimneys and Vents)
  47. 47Vent connectors shall be constructed of no thinner than galvanized ________GA, copper ____________B&S GA, and aluminum ____B&S GA.28
    26
    24
    (Chimneys and Vents)
  48. 48The minimum required thickness for a 6" diameter chimney connector for a low-heat appliance is No. __________ gage.24
    (Chimneys and Vents)
  49. 49The minimum required thickness for an 8" diameter chimney connector for a high-heat appliance is No. ___________ gage.16
    (Chimneys and Vents)
  50. 50The cross-sectional area of a flue serving a solid fuel-burning appliance shall be a maximum of ___________ times the cross sectional area of flue collar or outlet.3
    (Chimneys and Vents)
  51. 51For mechanical draft systems, where termination of a vertical vent occurs below an adjacent roof structure, the termination point shall be located a minimum of _____ feet from the structure3
    (Chimneys and Vents)
  52. 52Where refrigeration equipment is located outside a building and within ________ feet of a building, the equipment shall be regulated by the occupancy classification of the building.20
    (Refrigeration)
  53. 53For the purpose of regulating refrigeration systems, large mercantile occupancies are defined as as those facilities where more than ______ persons congregate to purchase personal merchandise.100
    (Refrigeration)
  54. 54In the mechanical ventilation of a machinery room, an exhaust system shall be discharged a minimum of ______ feet from a property line or any openings into buildings.20
    (Refrigeration)
  55. 55Steel pipe for Group A2, A3, B2, and B3 refrigerants shall have a minimum weight of Schedule 80 where a maximum of ____________ inch(es) in diameter.1 1/2
    (Refrigeration)
  56. 56Machinery rooms shall not have continuously operating hot surfaces over __________ degrees F permanently installed in the room.800
    (Refrigeration)
  57. 57Enclosures and pipe ducts for refrigerant piping are not required for connections between condensing units and the nearest riser box when the connections are a maximum of _______ feet in length.6
    (Refrigeration)
  58. 58Required field tests of refrigerant containing parts may be performed with __________ or ____________.nitrogen
    carbon dioxide
    (Refrigeration)
  59. 59Which of the following materials in a refrigerant system is permitted to be used in contact with R-40 (methyl chloride)?brass
    (Refrigeration)
  60. 60Unless protected from mechanical damage, soft annealed copper tubing larger than _____________ inch(es) shall not be used for field-assembled refrigerant piping.1 3/8
    (Refrigeration)
  61. 61An emergency ventilation system serving a machinery room shall discharge a minimum of ____________ feet from any window, ventilation opening or exit.20
    (Refrigeration)
  62. 62Field-fabricated copper brazed swaged fitting connections for refrigerant piping shall have a minimum cut depth of _____________ inch(es) where the fitting size is 3/4 inch..25
    (Refrigeration)
  63. 63Where a michinery room is provided with an emergency ventilation system, the point of discharge to the atmosphere outside the structure shall be a minimum of ______________ feet above the adjoining grade level.15
    (Refrigeration)
  64. 64In institutional occupancies, the maximum permitted total of all Group A2, B2, A3, and B3 refrigerants in occupied areas or machinery rooms is ____________ pounds.550
    (Refrigeration)
  65. 65A certificate of test shall be provided for all systems containing a minimum of ______ pounds of refrigerant.55
    (Refrigeration)
  66. 66Screens, louvers, or grilles that protect outdoor exhaust discharge shall not have openings sized less than _____ inch and not larger than _______ inch..25
    .5
    (Exhaust Systems)
  67. 67When installing a clothes dryer, installations exhausting more than ______ CFM shall be provided with makeup air.200
    (Exhaust Systems)
  68. 68Type _______ hoods do not produce grease or smoke as part of the cooking process.2
    (Exhaust Systems)
  69. 69Grease ducts shall be constructed of steel with the thickness of ______GA, or stainless steel with a thickness of ________ GA.16
    18
    (Exhaust Systems)
  70. 70When installing a clothes dryer in a closet area, an opening having an area of not less than ____________square inches must be provided.100
    (Exhaust Systems)
  71. 71When enclosures are not required, grease ducts and exhaust equipment serving type 1 hoods shall have clearance to combustibles of no less than _____ inches.18
    (Exhaust Systems)
  72. 72When there are exposed charcoal or char broil, grease filters must be at least _______ inches from the cooking source.42
    (Exhaust Systems)
  73. 73Name 3 acceptable grease duct joint types.________, __________ and ___________.butt joints
    welded flange joints(.5" depth max)
    overlapping joints (2" depth max)
    (Exhaust Systems)
  74. 74Exhaust ducts for type 1 hoods that terminate above the roof shall be not less than ______ inches above the roofs surface.40
    (Exhaust Systems)
  75. 75The minimum net airflow of a type 2 dishwasher hood shall be ______CFM per linear foot.100
    (Exhaust Systems)
  76. 76Type 2 hoods shall be constructed of ____GA steel, _____GA stainless steel.22
    24
    (Exhaust Systems)
  77. 77The maximum vertical distance between the front lower lip of a canopy type 1 hood and the appliance surface shall be _______ feet.4
    (Exhaust Systems)
  78. 78Hazardous exhaust ducts shall be supported at maximum intervals of _________ feet.10
    (Exhaust Systems)
  79. 79Where cooking appliances are required to have a type 1 hood, they must be provided with an approved _______.automatic fire suppression system
    (Exhaust Systems)
  80. 80All portions of active engineered smoke control systems shall be capable of continued operation after detection of the fire event for a minimum of ________ minutes, but not less than 1.5 times the calculated egress time.20
    (Exhaust Systems)
  81. 81As a portion of a refuse conveying system, an exhaust outlet serving a low heat appliance (800 degrees F) shall terminate a minimum of _______ feet above the roof opening.3
    (Exhaust Systems)
  82. 82Sub slab soil exhaust system ducts shall have a minimum slope of _______ percent.1
    (Exhaust Systems)
  83. 83In a stock conveying system, a single wall metal chimney serving a medium heat appliance shall terminate a minimum of ______ feet above any part of the building within 25 feet.10
    (Exhaust Systems)
  84. 84Non canopy type hoods shall be located a maximum of _________ feet above the cooking surface.3
    (Exhaust Systems)
  85. 85When using the airflow design method for a smoke control system, the maximum airflow toward a fire shall be ________ feet per minute.200
    (Exhaust Systems)
  86. 86Ducts and air transfer openings utilized as portions of a smoke control system are required to be protected with a minimum class 2 _________ degrees F smoke damper.250
    (Exhaust Systems)
  87. 87The bottom of an exhaust opening where fuels are dispensed shall be located not more than ______ inches above the floor.18
    (Exhaust Systems)
  88. 88Exhaust ventilation containing hazardous materials containing fumes and vapors heavier than air must be located within _______inches of the floor. Lighter than air ________ inches from the highest point in the room.12
    12
    (Exhaust Systems)
  89. 89Clothes dryer ducts shall be supported at _________ foot intervals.4
    (Exhaust Systems)
  90. 90Duct to hood joints in a grease duct shall be made with a ________________.continuous external or internal liquid tight weld or braize
    (Exhaust Systems)
  91. 91Grease ducts shall slope not less than _______per foot. Where grease ducts exceed 75' ________ per foot..25
    1
    (Exhaust Systems)
  92. 92Exhaust equipment serving a type 1 hood shall have a clearance to combustibles not les than ______ inches.18
    (Exhaust Systems)
  93. 93Type 2 exhaust terminations shall end not less than ______ feet above grade.10
    (Exhaust Systems)
  94. 94A type 1 hood shall be installed with clearance to combustibles of not less than _______ inches.18
    (Exhaust Systems)
  95. 95The minimum net airflow in type 2 dishwashing appliance is ______CFM per linear foot.100
    (Exhaust Systems)
  96. 96An exhaust duct exhausting a temperature of 100 to 600 degrees F shall have _______ inches clearance to combustibles.12
    (Exhaust Systems)
  97. 97An exhaust duct exhausting flammable vapors shall have _______ inches clearance to combustibles.6
    (Exhaust Systems)
  98. 98Exhaust gases having temperatures in excess of _______ degrees F shall be exhausted to a chimney.600
    (Exhaust Systems)
  99. 99Water heaters used for both potable water heating and space heating shall be sized to prevent the space-heating load from reducing the required _____________.potable water heating capacity
    (Boilers, Water Heaters, and Pressure Vessels)
  100. 100In sizing a cloosed-type expansion tank, ____________, _____________, and ______________ is required.average operating temperature
    fill pressure
    minimum operating pressure
    (Boilers, Water Heaters, and Pressure Vessels)
  101. 101Safety and relief valve discharge pipes for boilers shall be of ____________ pipe that is approved for the temperature of the system.rigid
    (Boilers, Water Heaters, and Pressure Vessels)
  102. 102Every steam boiler shall have a ___________ and a __________water-guage glass
    pressure guage
    (Boilers, Water Heaters, and Pressure Vessels)
  103. 103For an open-type hot water expansion tank, an overflow with a minimum diameter of __________ inch(es) shall be installed at the top of the tank.1
    (Boilers, Water Heaters, and Pressure Vessels)
  104. 104In the installation of a boiler, valves shall be located on ___________ of a safety or relief valve connection.neither side
    (Boilers, Water Heaters, and Pressure Vessels)
  105. 105During the testing of a boiler or pressure vessel, the indicating test guage shall have the pressure guage scale graduated over a range of not less than one and one-half times and not greater than __________ times the maximum test pressure.6
    (Boilers, Water Heaters, and Pressure Vessels)
  106. 106Open-type hot water boiler expansion tanks shall be located a minimum of ______________ feet above the highest heating element.4
    (Boilers, Water Heaters, and Pressure Vessels)
  107. 107Cooling towers and fluid coolers shall be provided with ____________.ready access
    (Specific Appliances, Fireplaces, and Solid Fuel-Burning Equipment)
  108. 108Cooling towers shall be located to prevent ____________ from entering occupied spaces.discharge vapor plumes
    (Specific Appliances, Fireplaces, and Solid Fuel-Burning Equipment)
  109. 109Unless adequately separated horizontally, plume discharges from cooling towers shall be a minimum of __________ feet above any ventilation inlets to a building.5
    (Specific Appliances, Fireplaces, and Solid Fuel Fuel-Burning Equipment)
  110. 110The location of the cooling towers on the property shall be as required in accordance with the "International __________ Code"Building
    (Specific Appliances, Fireplaces, and Solid Fuel-Burning Equipment)
  111. 111Floor furnaces shall be installed within ____________ inches from the nearest wall.6
    (Specific Appliances, Fireplaces, and Solid Fuel-Burning Equipment)
  112. 112Unless adequately separated vertically, plume discharges from cooling towers shall be a minimum of ____________ feet away from any ventilation inlets to a building.20
    (Specific Appliances, fireplaces, and Solid Fuel-Burning Equipment)
  113. 113Whe provided to control the main burner operation of a sauna heater, a timer shall have a maximum operating time of _______________ minutes.60
    (Specific Appliances, Fireplaces, and Solid Fuel-Burning Equipment)
  114. 114Sauna heaters shall be equipped with a thermostat that will limit room temperature to a maximum of ______________ degrees F.194
    (Specific Appliances, Fireplaces, and Solid Fuel-Burning Equipment)
  115. 115A ___________ shall be installed ahead of all controls for a vented wall furnace.manual shutoff valve
    (Specific Appliances, Fireplaces, and Solid Fuel-Burning Equipment)
  116. 116Access panels that must be removed for normal servicing operations on vented wall furnaces shall not ____________.be attached to the building construction
    (Specific Appliances, Fireplaces, and Solid Fuel-Burning Equipment)
  117. 117Where a relief valve is required in a solar energy system, the valve shall be set at a maximum of____________ percent of the nameplate pressure rating.100
    (Solar Thermal Systems)
  118. 118Sloar thermal system components subject to a vacuum during shutdown shall be protected with vacuum _____________ unless designed to withstand such vacuum.relief valves
    (Solar Thermal Systems)
  119. 119In general, solar thermal equipment exposed to vehicular traffic shall be installed a minimum of ___________ feet above the floor.6
    (Solar Thermal Systems)
  120. 120Where attics or structural spaces are used as part of a passive solar system, ___________ of such spaces is not required where other approved means of controlling condensation is provided.ventilation
    (Solar Thermal Systems)
  121. 121The minimum flash point of the heat transfer fluid utilized in a solar thermal system shall be _________ degrees F above the design maximum nonoperating temperature of the fluid attained in the collector.50
    (Solar Thermal Systems)
  122. 122A _________ shall not be used as a heat transfer fluid in a solar system.Class 1C flammable liquid
    (Solar Thermal Systems)
  123. 123In the process of installing any part of a solar thermal system, roof and wall penetrations shall be flashed and sealed to prevent entry of _________, ___________, and ______________.water
    rodents
    insects
    (Solar Thermal Systems)
  124. 124Where ducts are utilized in a solar heating system, air transported to occupied spaces through rock or dust-producing materials by means other than natural convection shall be filtered before entering the ___________.occupied space
    (Solar Thermal Systems)
  125. 125Roof-mounted solar collectors that serve as the roof covering shall conform to the requirements of the ___________ for roof coverings."International Building Code"
    (Solar Thermal Systems)
  126. 126Vent pipes from fuel oil tanks containing heaters shall be extended to a location where oil vapors discharging from the vent will ____________.be readily diffused
    (Fuel Oil Piping and Storage)
  127. 127If the static head with a vent pipe filled with fuel oil exceeds _________ pounds per square inch, the tank shallbe designed for the maximum imposed static head.10
    (Fuel Oil Piping and Storage)
  128. 128In a fuel oil piping system, test wells shall not be installed __________.inside a building
    (Fuel Oil Piping and Storage)
  129. 129In a fuel piping oil system, the guaging of inside tanks by means of ___________ shall not be permitted.measuring sticks
    (Fuel Oil Piping and Storage)
  130. 130Fill and vent pipes serving inside fuel oil tanks shall be provided with a device to indicate ____________ at the fill point when the oil in the tank has reached a predetermined safe level.either visually or audibly
    (Fuel Oil Piping and Storage)
  131. 131Pipe bends made in fuel oil piping shall not exceed the _____________ limitations of the pipe.structural
    (Fuel Oil Piping and Storage)
  132. 132Unions or other fittings requiring sweat fittings employing solder having a melting point of less than __________ degrees F shall not be used in oil lines.1,000
    (Fuel Oil Piping and Storage)
  133. 133The minimum size of pipe used in a return line of fuel oil piping system shall be _______________ inch(es) inside diameter.1/4
    (Fuel Oil Piping and Storage)
  134. 134Joints between steel fuel oil pipe shall be by any of the following methods, except ____________.brazed
    (Fuel Oil Piping and Storage)
  135. 135A fill pipie for fuel oil shall terminate outside of a building at a point a minimum of ___________ feet from any building opening at the same or lower level.2
    (Fuel Oil Piping and Storage)
  136. 136Provisions shall be made to prevent the formation of __________ on teh exterior of hydronic piping.condensation
    (Hydronic Piping)
  137. 137Embedded piping for heating panels, when of the approved plastic pipe or tubing, shall be rated at 100 psi at __________ degrees F.180
    (Hydronic Piping)
  138. 138When testing a plastic pipe ground source heat pump loop system, if the actual flow rate or pressure drop values differ from the calculated design value by more than ______________, the problem shall be identified and corrected.10 percent
    (Hydronic Piping)
  139. 139The transfer fluid in a hydronic piping system shall be compatible with the ____________ supplied to the system.makeup water
    (Hydronic Piping)
  140. 140The flash point of transfer fluid in a hydronic piping system shall be a minimum of ________ degrees F above the maximum system operating temperature.50
    (Hydronic Piping)
  141. 141Where a 1 inch CPVC piping is installed horizontally in a hydronic piping system, it shall be supported at maximum intervals of ____________ feet.3
    (Hydronic Piping)
  142. 142The exterior of hydronic pipe shall be protected from ___________.corrosion
    (Hydronic Piping)
  143. 143Valves used in a hydronic piping system shall be rated for the ____________ and ________________ of the system in which the valves are installed.temperatures
    pressures
    (Hydronic Piping)
  144. 144Joints and connections shall be tight for the ______________ of the hydronic system.pressure
    (Hydronic Piping)
  145. 145In the preparation of pipe ends of hydronic piping, the ends shall not be _____________.undercut
    (Hydronic Piping)
  146. 146Mechanical joints in hydronic piping shall be installed per the _____________.manufacturer's instructions
    (Hydronic Piping)
  147. 147The minimum duration of the test of a hydronic piping system shall be ___________ minutes.15
    (Hydronic Piping)
  148. 148In a hydronic piping system, shutoff valves shall be installed on ____________ of a pressure-reducing valve.both sides
    (Hydronic Piping)
  149. 149Insulating materials utilized in radiant floor heating systems must be installed such that the manufacturer's __________ is readily observable upon inspection.R-Value mark
    (Hydronic Piping)
  150. 150Openings for hydronic pipe penetrations through concrete or masonry building elements shall be ____________.sleeved
    (Hydronic Piping)