EPA 608 practice questions: Low-pressure leak detection
Finding leaks in low-pressure systems, and the methods that suit them.
Updated 17 November 2026 for the current EPA rules and Test Topics
Key facts
For a low-pressure leak test, prefer hot water or a built-in heating device to raise system pressure before using nitrogen.
US EPA, Section 608 Technician Certification: Test Topics, Type 3 (Low-pressure) test: Leak Detection
Excessive purging can indicate that air is leaking into a low-pressure system.
US EPA, Section 608 Technician Certification: Test Topics, Type 3 (Low-pressure) test: Leak Detection
Do not exceed the applicable maximum leak-test pressure for a low-pressure centrifugal chiller.
US EPA, Section 608 Technician Certification: Test Topics, Type 3 (Low-pressure) test: Leak Detection
Owners or operators must take corrective action when an appliance with a full charge of 50 or more pounds of ozone-depleting refrigerant exceeds its applicable trigger leak rate.
US EPA, Stationary Refrigeration Leak Repair Requirements, Stationary Refrigeration Leak Repair Requirements
The 12-month trigger leak rate is 30 percent for industrial process refrigeration and 20 percent for commercial refrigeration.
US EPA, Stationary Refrigeration Leak Repair Requirements, Stationary Refrigeration Leak Repair Requirements
The 12-month trigger leak rate is 10 percent for comfort cooling and for other appliances.
US EPA, Stationary Refrigeration Leak Repair Requirements, Stationary Refrigeration Leak Repair Requirements
In general, owners or operators must repair leaks within 30 days of discovery or develop a retrofit or retirement plan within 30 days.
US EPA, Stationary Refrigeration Leak Repair Requirements, Stationary Refrigeration Leak Repair Requirements (part 3)
In general, a retrofit or retirement plan must be completed within one year of the plan date.
US EPA, Stationary Refrigeration Leak Repair Requirements, Stationary Refrigeration Leak Repair Requirements (part 3)
Owners or operators of covered appliances exceeding the trigger rate must conduct initial and follow-up verification tests of repairs.
US EPA, Stationary Refrigeration Leak Repair Requirements, Stationary Refrigeration Leak Repair Requirements (part 3)
Sample questions
1. A technician needs to pressurize a low-pressure chiller for leak testing. Which method should be tried before adding nitrogen?
- Add dry nitrogen to the system
- Add compressed air to the system
- Warm the system with hot water
- Pressurize the system with oxygen
Answer: C. Warm the system with hot water
Hot water is a preferred way to raise pressure for leak testing a low-pressure system. Nitrogen is considered after the heating methods.
- Add dry nitrogen to the system: Nitrogen is considered after the preferred heating methods.
- Add compressed air to the system: Compressed air can introduce moisture and is not a preferred test gas.
- Pressurize the system with oxygen: Oxygen can create a fire or explosion hazard.
Source: US EPA, Section 608 Technician Certification Test Topics page: topic lists for Core, Type 1, Type 2 and Type…, Type 3 (Low-pressure) test: Leak Detection
2. A low-pressure chiller has a built-in heating device designed for pressurization. How does that device fit into the leak-test pressurization order?
- Use it only after nitrogen has been added
- Use it only after compressed air has been added
- Consider it only after adding oxygen
- Consider it before adding nitrogen
Answer: D. Consider it before adding nitrogen
A built-in heating or pressurization device is a preferred method for raising pressure before leak testing. It is considered before adding nitrogen.
- Use it only after nitrogen has been added: The built-in device is considered before nitrogen.
- Use it only after compressed air has been added: Compressed air is not a preferred pressurizing gas.
- Consider it only after adding oxygen: Oxygen is unsafe for this purpose.
Source: US EPA, Section 608 Technician Certification Test Topics page: topic lists for Core, Type 1, Type 2 and Type…, Type 3 (Low-pressure) test: Leak Detection
3. A low-pressure chiller's purge unit runs much more often than usual. What should the technician suspect?
- Air is leaking into the system.
- Refrigerant is overcharging the evaporator.
- The liquid line is overfeeding refrigerant.
- Oil is leaking into the condenser water.
Answer: A. Air is leaking into the system.
Excessive purging can indicate that air is leaking into a low-pressure system. The purge unit removes noncondensable gases that collect in the chiller.
- Refrigerant is overcharging the evaporator: An overcharged evaporator does not explain air entering the system.
- The liquid line is overfeeding refrigerant: Overfeeding refrigerant does not explain excessive noncondensable gas.
- Oil is leaking into the condenser water: Oil in condenser water does not explain excessive purge operation.
Source: US EPA, Section 608 Technician Certification Test Topics page: topic lists for Core, Type 1, Type 2 and Type…, Type 3 (Low-pressure) test: Leak Detection
4. A low-pressure chiller operates below atmospheric pressure and has a leak. What can enter through the leak?
- Air and moisture from the surrounding space
- Liquid refrigerant from the recovery cylinder
- Compressor oil from the external reservoir
- Condenser water from an external drain
Answer: A. Air and moisture from the surrounding space
When system pressure is below atmospheric pressure, a leak can allow air and moisture to enter. This can increase the load on the purge unit.
- Liquid refrigerant from the recovery cylinder: A recovery cylinder is not the surrounding source of air leakage.
- Compressor oil from the external reservoir: An external oil reservoir is not the usual source of air leakage.
- Condenser water from an external drain: An external drain does not normally supply water through an air leak.
Source: US EPA, Section 608 Technician Certification Test Topics page: topic lists for Core, Type 1, Type 2 and Type…, Type 3 (Low-pressure) test: Leak Detection