EPA 608 practice questions: Low-pressure leak detection

Finding leaks in low-pressure systems, and the methods that suit them.

12 questions · 9 key rules

Updated 17 November 2026 for the current EPA rules and Test Topics

Key facts

Sample questions

Tap a question to see the answer and the rule behind it.
  1. Type III leak detect.1. A technician needs to pressurize a low-pressure chiller for leak testing. Which method should be tried before adding nitrogen?
    1. Add dry nitrogen to the system
    2. Add compressed air to the system
    3. Warm the system with hot water
    4. Pressurize the system with oxygen
    Show answer and explanation

    Answer: C. Warm the system with hot water

    Hot water is a preferred way to raise pressure for leak testing a low-pressure system. Nitrogen is considered after the heating methods.

    Why the others are wrong

    • Add dry nitrogen to the system: Nitrogen is considered after the preferred heating methods.
    • Add compressed air to the system: Compressed air can introduce moisture and is not a preferred test gas.
    • Pressurize the system with oxygen: Oxygen can create a fire or explosion hazard.

    Source: US EPA, Section 608 Technician Certification Test Topics page: topic lists for Core, Type 1, Type 2 and Type…, Type 3 (Low-pressure) test: Leak Detection

  2. Type III leak detect.2. A low-pressure chiller has a built-in heating device designed for pressurization. How does that device fit into the leak-test pressurization order?
    1. Use it only after nitrogen has been added
    2. Use it only after compressed air has been added
    3. Consider it only after adding oxygen
    4. Consider it before adding nitrogen
    Show answer and explanation

    Answer: D. Consider it before adding nitrogen

    A built-in heating or pressurization device is a preferred method for raising pressure before leak testing. It is considered before adding nitrogen.

    Why the others are wrong

    • Use it only after nitrogen has been added: The built-in device is considered before nitrogen.
    • Use it only after compressed air has been added: Compressed air is not a preferred pressurizing gas.
    • Consider it only after adding oxygen: Oxygen is unsafe for this purpose.

    Source: US EPA, Section 608 Technician Certification Test Topics page: topic lists for Core, Type 1, Type 2 and Type…, Type 3 (Low-pressure) test: Leak Detection

  3. Type III leak detect.3. A low-pressure chiller's purge unit runs much more often than usual. What should the technician suspect?
    1. Air is leaking into the system.
    2. Refrigerant is overcharging the evaporator.
    3. The liquid line is overfeeding refrigerant.
    4. Oil is leaking into the condenser water.
    Show answer and explanation

    Answer: A. Air is leaking into the system.

    Excessive purging can indicate that air is leaking into a low-pressure system. The purge unit removes noncondensable gases that collect in the chiller.

    Why the others are wrong

    • Refrigerant is overcharging the evaporator: An overcharged evaporator does not explain air entering the system.
    • The liquid line is overfeeding refrigerant: Overfeeding refrigerant does not explain excessive noncondensable gas.
    • Oil is leaking into the condenser water: Oil in condenser water does not explain excessive purge operation.

    Source: US EPA, Section 608 Technician Certification Test Topics page: topic lists for Core, Type 1, Type 2 and Type…, Type 3 (Low-pressure) test: Leak Detection

  4. Type III leak detect.4. A low-pressure chiller operates below atmospheric pressure and has a leak. What can enter through the leak?
    1. Air and moisture from the surrounding space
    2. Liquid refrigerant from the recovery cylinder
    3. Compressor oil from the external reservoir
    4. Condenser water from an external drain
    Show answer and explanation

    Answer: A. Air and moisture from the surrounding space

    When system pressure is below atmospheric pressure, a leak can allow air and moisture to enter. This can increase the load on the purge unit.

    Why the others are wrong

    • Liquid refrigerant from the recovery cylinder: A recovery cylinder is not the surrounding source of air leakage.
    • Compressor oil from the external reservoir: An external oil reservoir is not the usual source of air leakage.
    • Condenser water from an external drain: An external drain does not normally supply water through an air leak.

    Source: US EPA, Section 608 Technician Certification Test Topics page: topic lists for Core, Type 1, Type 2 and Type…, Type 3 (Low-pressure) test: Leak Detection